4 Start-Up
F2 DO 16 01
Page 28 of 40
HI 800 159 E Rev. 1.01
4.4.3 Digital
Outputs for F2 DO 16 01
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0x005A [90
dec
]
Mod. Error Code
[WORD]
R Module
error
code
Coding
Description
0x0000
I/O processing, if required with errors, see other error
codes
0x0001
No I/O processing (remote I/O not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: incorrect configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
DOy.Error Code
[WORD]
R
Error codes for all digital outputs
Coding
Description
0x0001
Fault within the digital outputs
0x0002
MOT test of safety shutdown returns a fault
0x0004
MOT test of auxiliary voltage returns a fault
0x0008
FTT test of test pattern faulty
0x0010
MOT test of output switch test pattern faulty
0x0020
MOT test of output switch test pattern (shutdown test
of the outputs) faulty
0x0040
MOT test active shutdown via WD faulty
0x0100
Outputs 1...4 and 9...12 de-energized due to total
current overrun
0x0200
Outputs 5...8 and 13...16 de-energized due to total
current overrun
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Low voltage
0x2000
FTT test: Monitoring of auxiliary voltage 2:
Low voltage
DOy
[
xx
]
.Error Code
[BYTE]
R
Error codes for the digital output channels
Coding
Description
0x01
Fault in the digital output module
0x02
Channel shutdown due to overload
0x04
Error while reading back the digital outputs
0x08
Error while reading back the status of the digital
outputs
DOy[xx].Value
[BOOL]
W
Output value for DO channels:
1 = output energized
0 = output de-energized
Table 18: ELOP II Factory - Digital Output System Signals
Содержание HIMatrix F2 DO 16 01
Страница 34: ...9 Disposal F2 DO 16 01 Page 34 of 40 HI 800 159 E Rev 1 01...
Страница 39: ......