CIO 2/4 01
4 Start-Up
HI 800 199 E Rev. 1.00
Page 23 of 40
4.3.1
Parameters and Error Codes for the Inputs and Outputs
The following tables specify the system parameters that can be read and set for the inputs
and outputs, including the corresponding error codes.
In the user program, the error codes can be read using the variables assigned within the
logic.
The error codes can also be displayed in SILworX.
4.3.2
Counter and Outputs CIO 2/4 01
The following tables present the statuses and parameters for the counter and the output
module in the same order as given in the Hardware Editor.
4.3.2.1
Module
Tab
The
Module
tab contains the following system parameters.
System parameter
Data
type
R/W Description
DO.Error Code
[WORD]
WORD
R
Error codes for all digital outputs
Coding
Description
0x0001 Module
fault
0x0002
MOT test safety switch 1 faulty
0x0004
MOT test safety switch 2 faulty
0x0008
FTT test of test pattern faulty
0x0010
MOT test of the read back channels faulty
0x0020
MOT test active shutdown faulty
0x0100
FTT test of CS (chip select) signals faulty
0x0200
All outputs are switched off, total current
exceeded
0x0400
FTT test: 1st temperature threshold
exceeded
0x0800
FTT test: 2nd temperature threshold
exceeded
0x1000
FTT test: Monitoring of auxiliary voltage 1:
Low voltage
0x2000
MOT test: status of safety switches
Module Error Code
[WORD]
WORD R Module
error
code
Coding
Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: wrong configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
[UDINT]
UDINT
R
Slot number (System Rack Slot)
Module Type [UINT]
UINT
R
Type of module, target value: 0xFC03 [64515
dec
]