F3 DIO 16/8 01
4 Start-up
HI 800 177 E Rev. 2.00
Page 39 of 60
4.3.3.2
Tab:
DO 8 03: Channels
The DO 8 03: Channels tab contains the following system parameters.
System parameter
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> + Error Code
[WORD]
WORD R
-> - Error Code
[WORD]
WORD R
Error codes for the digital output channels DO+
Error codes for the digital output channels DO-
Coding
Description
0x0001
Fault in the digital output module
0x0002
Channel shutdown due to overload
0x0004
Error while reading back the digital outputs
0x0008
Error while reading back the status of the
digital outputs
0x0010 Short-circuit
0x0020
Channel is switched off due to fault on the
corresponding channel
0x0040
Z-diode are destroyed at the output
0x0080 Open-circuit
0x0100
Test of the output switches provides in DO+
line causes an error
0x0200
Test of the output switches provides in DO-
line causes an error
0x0400
Test of the test switches L- causes an error
0x0800
External supply L+ at DO+
+ Value [BOOL] ->
BOOL
W
Output value for DO+ channels, 1-pole (value: 0 or 1)
Output value for DO+ channels, 2-pole, identical to DO-
(Value: 0 or 1)
- Value [BOOL] ->
BOOL
W
Output value for DO- channels, 1-pole (value: 0 or 1)
Output value for DO- channels, 2-pole, identical to DO+
(Value: 0 or 1)
2-pole [BOOL] ->
BOOL
W
Configuration for a 2-Pole channel
Coding
Description
FALSE
Channel used for a 1-pole
TRUE
Channel used for a 2-pole
Line Monitoring
[BOOL] ->
BOOL
W
Configuration of Line Diagnosis
Coding
Description
FALSE LSLB
1)
diagnosis is not performed
TRUE LSLB
1)
diagnosis is performed
1)
SC/OC (SC = short-circuits, OC = open-circuits)
Table 27: SILworX - System Parameters for Digital Outputs,
DO 8 03: Channels
Tab