F3 DIO 16/8 01
4 Start-up
HI 800 177 E Rev. 2.00
Page 31 of 60
4.1.3.1
Overview of Configuration Variants for the Digital Outputs
The following table specifies all configuration variants permitted for the digitals outputs.
Additional system signals have no influence on other variants (e.g.,
Signal DO[xx].SC
monitoring with reduced voltage
). With improper parameter setting, a diagnostic entry (
IOA
Wrong Initial Data
) is generated. Simultaneously, the parameter setting is displayed. Use the
table below to locate errors.
Configuration Variants with Digital Outputs
Application
Channel 1
2-pole
Channel 2
2-pole
Channel 1
SC/OC
Channel 2
SC/OC
Common
ground
1-pole
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
2-pole
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
X
1)
3-pole
X
1)
X
1)
X
1)
X
1)
X
1)
1)
Option
is
selected
SC/OC: Line diagnosis (SC = short-circuit, OC = open-circuit)
Table 20: Configuration Variants with Digital Outputs
4.1.4
Pulsed Outputs
Terminal assignment for the pulsed outputs.
Terminal
Designation
Function (non-safe pulsed outputs TO)
25
1
Pulsed output 1
26
1
Pulsed output 1
27
1
Pulsed output 1
28
1
Pulsed output 1
29
2
Pulsed output 2
30
2
Pulsed output 2
31
2
Pulsed output 2
32
2
Pulsed output 2
Table 21: Terminal Assignment for the Pulsed Outputs