NOTE
Depending on the version purchased, the slope adapter
and markers may not be included among the items sup-
plied.
2.3 Measuring principle
2
The transmitter generates a magnetic field. This magnetic
field is capable of penetrating, bricks, wood, concrete
and steel reinforced concrete. The receiver is calibrated
in such a way that it finds the center point of the projected
field and determines the applicable distance by measur-
ing the strength of the magnetic field between the two
units of the tool. The slope adapter has been designed for
use together with the transpointer so that the magnetic
field can be measured even when the receiver is placed
at an angle to the transmitter.
NOTE
The PX 10 transpointer is influenced by metal objects.
Whereas symmetrically arranged steel reinforcement in
concrete presents virtually no problem, welded reinforce-
ment, reinforcing mesh, flat sheet metal or solid metal
columns have a very negative effect on the performance
of the system.
3 Consumables
Accessories
Designation
Item number
Adhesive putty
PUA 91
273131
Adhesive strips
PUA 92
273132
Hand strap
PDA 60
282389
Slope adapter
PXA 70
273130
Markers
PUA 70
340806
4 Technical data
Right of technical changes reserved.
NOTE
The proximity of welded reinforcement, sheet metal or metal framing to the tool may have a considerable negative
effect on its accuracy. When wall thickness measurements are made through welded reinforcing mesh, the distance
displayed is approx. 20% greater. At temperatures below -10 °C (14 °F) considerable inaccuracy may occur with wall
thicknesses greater than 50 cm (1.64 ft).
Technical data
Values
Position-finding accuracy, standard (up to max. 1 m /
3 ft 3 in)
Tempe21°C (+70°F), Wall thickness 200 mm:
±8 mm (7.87 in: 0.32 in)
Position-finding accuracy, maximum (up to maximum
1 m / 3 ft 3 in, without influence by metal objects)
Tempe21°C (+70°F), Wall thickness 200 mm:
±2 mm (7.87 in: 0.08 in)
Wall thickness measurement accuracy (up to maximum
1 m / 3 ft 3 in, except when using the slope adapter)
Tempe21°C (+70°F): ±5 %
Measurement range (standard)
0.05…1.35 m (2 in to 4 ft 5 in)
Operating temperature (PX 10T, PX 10R, PUA 91)
-20…+55°C (-4 °F to +131 °F)
Operating temperature (PUA 92)
+10…+40°C (+50 °F to +104 °F)
Storage temperature
-25…+70°C (-13 °F to +158 °F)
Power source (PX 10T, PX 10R)
One 9 V battery in each
Battery life (PX 10T, PX 10R)
Tempe21°C (+70°F): 17 h
Automatic cut-out, PX 10T
17 min
Automatic cut-out, PX 10R
Without change in signal: 3 min, With change in signal:
8 min
Low battery indication (PX 10T)
Status indicator blinks: Remaining operating time: Min.
2 h