The interface on connector X3 of the PKV 30-DPS is designed for 

communication 

respectively for

diagnostic/configuration

If the power of the protocol converter is switched on, it checks the serial interface
if the diagnostic/configuration mode should be activated, otherwise it starts the
communication mode. 

2.4.1 Activation of the Diagnostic/Configuration Mode 

Connect the diagnostic cable on X3 of the protocol converter and to COM1 (or
COM2) of the PC. 

Start the program ComPro 

COMPRO /S:1   

respectively.

   COMPRO /S:2

(for COM1 respectively COM2). 

Select menu 

online - system - bootstart. 

A windows appears that shows 

The sy-

stem will be reseted and the bootloader becomes active without starting any
firmware

Turn off power of the protocol converter and wait at least 10 seconds. 

Accept the message 

The system will be reseted and the bootloader becomes acti-

ve without starting any firmware

 with press the Enter key. A red window appears

that shows 

Waiting for hardware receipt

Power on the protocol converter. 

The red window disappears. 

To test if the protocol converter is in diagnostic/configuration mode select menu

online system - firmware.

 If a window appears and shows the name of the firm-

ware, then the diagnostic/configuration mode is active. If the message 

Connection

could not be established or connection lost

 appears, then try to activate the dia-

gnostic/configuration mode again according to the steps described above. 

If the interface is configured as
RS422 or RS485 it is 

not

necessary

 to change for the dia-

gnostic mode.

General device description

14

Copyright * Hilscher Gesellschaft für Systemautomation mbH * Hotline/Support: +49(0)6190/9907-99 * De:P30DPS#5E

Содержание PKV 30-DPS

Страница 1: ...slave Hilscher Gesellschaft f r Systemautomation mbH Rheinstra e 78 D 65795 Hattersheim Germany Tel 49 0 6190 9907 0 Fax 49 0 6190 9907 50 Sales 49 0 6190 9907 0 Hotline and Support 49 0 6190 9907 99...

Страница 2: ...h great care and intensively tested Hilscher Gesellschaft f r Systemautomation mbH cannot guarantee the suitability of this appliance for any purpose not confir med by us in writing Guarantee claims s...

Страница 3: ...nnection of the Power Supply X1 8 2 3 Serial Interfaces 9 2 3 1 First Serial Interface X3 9 2 3 2 Potential free RS485 PROFIBUS Interface X2 11 2 4 Diagnostic Interface 13 2 4 1 Activation of the Diag...

Страница 4: ...m which is hardly capable of functioning In spite of the greatest possible care it then happens that an error on ly becomes apparent when the plant is in service Particularly when the error oc curs sp...

Страница 5: ...an be configured as RS232 RS422 or RS485 type The second isolated interface is designed for the PROFIBUS DP The correct function of the protocol converter and its internal power supply are monitored b...

Страница 6: ...icture will show the position of the jumper seeing from the side of the converter With the help of the table you can chose the right type of interface selection jumper J2 interface open RS232 3 4 RS48...

Страница 7: ...ation can be downloaded The bootstart mode can be activated when J1 is closed The device activates the bootstart mode when the power supply is reconnected In this mode only a firm waredownload can be...

Страница 8: ...fficient The power supply must be earth grounded The power supply are connected by means of a plug in screw terminal A 3 way COMBICON plug from PHOENIX MSTB 2 5 3 ST 5 08 is used pin symbol signal 1 2...

Страница 9: ...iagnostic configuration of the protocol converter The activation of the diagnostic configuration mode is described in chapter acti vation of the diagnostic configuration mode in this manual 4 3 1 2 6...

Страница 10: ...utput RXD TXD N TXD N transmit data inverted RS 422 data inverted RS485 2 input RXD receive data RS 232 3 output TXD transmit data RS 232 4 input RXD P receive data RS 422 5 RGND reference potential a...

Страница 11: ...1 2k RXD TXD N ISO 5V ISO 5V ISO 5V ISO 5V DGND DGND 5V 5V GND RGND2 RXD TXD P ISOGND ISOGND ISOGND TX RTS RX RS485 PROFIBUS interface at connector X2 Resistors R31 and R32 set a closed level on the...

Страница 12: ...itive supply voltage VP 7 not connected 8 send receive data inverted RxD TxD N RS485 9 not connected Pinning of the 9 way D Sub plug for the PROFIBUS DP on X2 Pin 1 in not for the connection of the pr...

Страница 13: ...ub connector A 9 way D Sub connector to DIN 41652 is used Data transfer between the PC and the protocol converter takes place at 9600 Baud and uses the following data format 8 data bits 1 stop bit and...

Страница 14: ...l converter and wait at least 10 seconds Accept the message The system will be reseted and the bootloader becomes acti ve without starting any firmware with press the Enter key A red window appears th...

Страница 15: ...while the firmware is being loaded Stays the LED off the may be a defect If a parameterization error is detected by a protocol task the task is displayed by the RUN LED as shown in the illustration be...

Страница 16: ...nsions and the arrangement of the plug connectors are shown in the drawings below Connector arrangement on the protocol converter Physical dimensions of the protocol converter for snap mounting to a m...

Страница 17: ...agnostic interface PROFIBUS interface RS485 PROFIBUS DP interface potential free max data transmission 12 MBaud Display LEDs system running and communication running or communication error on serial i...

Отзывы: