Device Picture, Connectors and LEDs
29/72
SmartWire-DT Gateway | EU5C-SWD-POWERLINK
DOC130802UM02EN | Revision 2 | English | 2013-12 | Released | Public
© Hilscher 2013
4.2.2
Descriptions of the LEDs
LED
Color
State
Meaning
Duo-LED yellow/green
(yellow)
On
Bootloader netX (= rom loader) is waiting for Second Stage
Bootloader.
(green/yellow)
Flashing
green/yellow
Second Stage Bootloader is waiting for firmware.
(green)
On
Operating system running, firmware is started.
POW
System
status
Number in
picture:
(off)
Off
Power supply for device is missing or hardware is defect.
Duo-LED red/green
(green)
On
Communication on POWERLINK and SmartWire-DT is in cyclic data
exchange and the gateway function is executed.
(green)
Flashing
1 s off,
1 s on
Gateway is initialized, but the communication on POWERLINK and
SmartWire-DT is not in cyclic data exchange.
(red)
Flashing
1 s off,
1 s on
Gateway is initialized, but the SmartWire-DT configuration is
missing or in error.
APL
Application
status
Number in
picture:
(red)
On
Gateway has detected an error during the initialization: Missing
configuration, error in configuration or internal error.
Duo-LED red/green
(green)
On
The project configuration complies with the target configuration.
Data exchange between gateway and PLC via POWERLINK is
possible.
(green)
Flashing
The project configuration does not comply with the target
configuration, but is compatible with it.
Data exchange between gateway and PLC via POWERLINK is
possible.
(red)
On
The project configuration and the target configuration are not
compatible.
Data exchange between gateway and PLC via POWERLINK
is not
possible
.
Config.
Configuration
status
Number in
picture:
(off)
Off
No communication with the POWERLINK PLC, or the gateway does
not have a project configuration.
Table 9: Description of the LEDs (1)