Technical Data
73/78
COMX Communication Modules | Design Guide
DOC100901DG18EN | Revision 18 | English | 2013-12 | Released | Public
© Hilscher, 2002-2013
4.1.16 COMX 100CN-CO
Immunity COMX 100CN-CO
Generic Standard
Basic Standard Test
Test level
Error
Class
Electrostatic Discharge
Air discharge
+ 10 kV
B
EN 61000-4-2
Contact discharge
+ 6 kV
B
Burst
EN 61000-4-4
Communication lines
+ 2 kV
fr = 5 kHz
A
Surge
EN 61000-6-2 (2006-03)
Industrial Environment
EN 61131-2 (2008-04)+A11, A12
Programmable Controllers
EN 61000-4-5
Communication lines (shielded)
1 kV
2 Ohm / 18
μ
F
A
Table 60: Product Tests COMX 100CN-CO – Immunity
4.1.17 COMX 100CN-DN
Immunity COMX 100CN-DN
Generic Standard
Basic Standard Test
Test level
Error
Class
Electrostatic Discharge
Air discharge
+ 10 kV
B
EN 61000-4-2
Contact discharge
+ 6 kV
B
Burst
Communication lines (shielded)
+ 2 kV
fr = 5 kHz
B
EN 61000-4-4
DeviceNet 24 V power supply
(unshielded)
+ 2 kV
fr = 5 kHz
B
Surge
Communication lines (shielded)
1 kV
2 Ohm / 18
μ
F
B
DeviceNet 24 V power supply
(unshielded) (24 V---PE, GND---PE)
1 kV
B
EN 61000-6-2 (2006-03)
Industrial Environment
EN 61131-2 (2008-04)+A11, A12
Programmable Controllers
EN 61000-4-5
DeviceNet 24 V power supply
(unshielded) (24 V---GND)
0,6 kV
B
Table 61: Product Tests COMX 100CN-DN – Immunity