Diagnosis
122/154
11.2 Diagnosis via EtherNet/IP
The IO-Link Wireless Master device NFD-3090-EIS-IOLM\W contains the
Event Log object with information about IO-Link events. The PLC can read
attributes of the Event Log object, in order to get the „Event Qualifier“ and
„Event Code“ of an IO-Link Event. Each IO-Link port has an assigned
instance.
Section
page 122] describes the attributes of
the object.
11.2.1
Event Log Object 65 (0x41)
The Event Log Object contains information on IO-Link events.
Instance 0 (class attributes)
Attribute Name
NV
Access
Data type Description
Default
1 (0x01)
Revision
NV
Get
UINT
Revision of this object
1
2 (0x02)
Max. instance NV
Get
UINT
Number of IO-Link ports
Number of
available IO-Link
ports
32 (0x20) Time Format
NV
Get
USINT
Data type identifier of the time format
Only THE STIME data type is supported.
204 (0xCC) =
STIME
33 (0x21) Present Time
NV
Get
STIME
Default for time value
Applies to all instances.
0
Table 86: Class attributes event log object 65 (0x41)
Instances 100, 101, … (instance attributes)
The following table shows the mapping of CIP instances to the IO-Link
ports.
IO-Link port
CIP instance
1
100
2
101
3
102
…
…
Table 87: Mapping CIP instances to IO-Link ports
The following table describes the attributes of the instances 100, 101, …
Attribute Name
NV
Access
Data type Description
Default
2 (0x02)
State
V
Get
USINT
State of this instance
0: Does not exist
1: Stopped
2: Empty
3: Available
4: Full/Override
5: Full/Stopped
6 – 255: Reserved
-
NFD-3090-EIS-IOLM\W | Hardware, installation and commissioning
DOC200701UM02EN | Revision 2 | English | 2021-08 | Released | Public
© Hilscher 2020 - 2021