122
Appendix 7 12VDC Wire Gauge & Transmission Distance
The following table describes the recommended max. distance adopted for the certain wire gauge
when the loss rate of 12VDC voltage is less than 15%. For the DC driven device, the maximum voltage
loss rate is 15% allowable.
0.800(20)
1.000(18)
1.250 (16)
2.000(12)
10
97(28)
153(44)
234(67)
617(176)
20
49(14)
77(22)
117(33)
308(88)
24
41(12)
64(18)
98(28)
257(73)
30
32(9)
51(15)
78(22)
206(59)
40
24(7)
38(11)
59(17)
154(44)
48
20(6)
32(9)
49(14)
128(37)
50
19(6)
31(9)
47(13)
123(35)
60
16(5)
26(7)
39(11)
103(29)
70
14(4)
22(6)
33(10)
88(25)
80
12(3)
19(5)
29(8)
77(22)
90
10.8(3.1)
17(5)
26(7)
69(20)
100
9.7(2.8)
15(4)
23(7)
62(18)
110
8.9(2.5)
14(4)
21(6)
56(16)
120
8.1(2.3)
13(4)
20(6)
51(15)
130
7.5(2.1)
11.8(3.4)
18(5)
47(14)
140
7(2)
11(3.1)
17(5)
44(13)
150
6.5(1.9)
10.2(2.9)
16(4)
41(12)
160
6.1(1.7)
9.6(2.7)
15(4)
39(11)
170
5.7(1.6)
9(2.6)
14(4)
36(10)
180
5.4(1.5)
8.5(2.4)
13(4)
34(10)
Distance
(feet)
Wire Gauge
(mm)
Power (va)