Electrical installation:

Main electrical installation must be protected against short circuit with e.g. circuit breaker: max.16A, 400Vac, Type B and installation must be
constructed properly according to valid national directives. 

First install the device on the application, than connect the protective earth!

Means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

The fan is intended only to be connected to the fixed wiring or application’s circuit. An all-pole separating switch which must be incorporated to wiring
must disconnect also the fan.

This product can cause a d.c. current in the protective earthing conductor. Where a residual current-operated protective device (RCD) or monitoring
(RCM) device is used for protection in case of direct or indirect contact, only an RCD or RCM of Type B+ is allowed on the supply side of this product
and recommended sensitivity is 300mA with short time delayed intervention.

The electrical connection must correspond to the enclosed connection diagram.

Recommended cable for power supply and alarm-relay contact is an ordinary PVC cable acc. to IEC 60227-5 (eg. H05V2V2-F, 4G 1 mm² or 6G 1 mm²
), no longer than 2m, outer diameter 4.5 - 9.5mm. 
Recommended cable for control circuit is an ordinary PVC cable (eg. H05VV-F, 5X 0,5 mm²) , no longer than 2m, outer diameter 4.5 - 9.5mm and must
be sufficient separated from the supply circuit. 
Ends of stranded wires needs to be provided with insulated ferrule (pin). Easier way to connect wires to the terminals if you use a screwdriver of
2.5x0.4mm dimensions to press the spring of terminal first and then insert the wire into the WAGO PUSH-WIRE® terminal. A screwdriver of 2.5x0.4mm
is necessary tool to remove conductor from the terminal.
Fan performed with terminal box is as supplied fitted with a sealing plug in the cable glands as a preventive against ingress of water or moisture inside
the terminal box. If the cable is not installed through the cable gland, sealing plug must remain in the gland!

Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so that the water flows away from the cable and cable gland.
Try to maintain as much distance between supply and control cable as possible (recommended distance > 5cm). 

Cable-end of the fan must be connected in a dry environment to prevent that water penetrate through cable into motor housing.

Where the fan is installed in shaft-horizontal position, the cable exit on the motor must be in down position.

Before putting into operation, check the resistance of protective-earth circuit of the entire application. Cross-sectional area and material of PE conductor
may be the same as cross-sectional of phase conductor or see guide regarding PE conductor : standard EN 61800-5-1. 

A second protective earthing conductor must be installed to ensure requirements of standard "

EN 61800-5-1 , 4.3.5.5.2 Touch current in case of failure

of protective earthing conductor

". For that purpose an additional M4 of 12mm depth hole or additional PE terminal is provided on motor housing and

marked with PE symbol. More information about dimensions of second PE conductor please find in guidelines of mentioned EN or equivalent standard

(a cross-section of second Cu conductor should never be less than 2.5mm

2

).

CONNECTING DIAGRAM : See appended technical drawing - CONNECTING DIAGRAM   0302-0-1008

POWER SUPPLY : L1, L2, L3, PE
Alarm relay: (COM) - (NC) , not SELV

CONTROL CIRCUIT:

Control circuit is SELV isolated from main power supply (including an external power supply for sensors).

Modbus : (RS A) - (RS B)
0-10V analog input : (0..10V) - (COM)
Sensor supply : (+10V) - (COM)
Slave control : (OUT) - (GND)

The device is compatible with Modbus protocol RTU. Please read additional instructions about Hidria EC Modbus parameters and additional information
for general purpose using MODBUS (www.modbus.org) .

WARNING : Leakage current exceeds 3.5mA.

Short circuit rating: <10kA .

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

6 / 9

Содержание 0314-4-0166

Страница 1: ...G INTO OPERATION 07 DIAGNOSTICS TROUBLESHOOTING 08 PROTECTIVE FEATURES 09 MAINTENANCE SERVICE AND CLEANING 10 TRANSPORT AND STORAGE 11 ErP ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL D...

Страница 2: ...nnot cause serious damage or bodily harm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance...

Страница 3: ...s appliance is not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be...

Страница 4: ...53 5 Installation category A Efficiency category static Efficiency grade N 60 3 Variable speed drive INTEGRATED Power Input Pelec 858 5 W Airflow volume qV 9867 m h Pressure Increase ps 161 Pa Rotati...

Страница 5: ...that the air gap between the fan impeller and the stationary housing is constant Distortion due to an uneven surface of basis may lead to a fan failure Air gap between blade and cone inlet housing sh...

Страница 6: ...ss of water or moisture inside the terminal box If the cable is not installed through the cable gland sealing plug must remain in the gland Secure connection cable to the fan guard grill or to the mot...

Страница 7: ...ighest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In order to ac...

Страница 8: ...upply voltage inadequate control signal or fan overheating Check line voltage check control signal check temperature and sufficient airflow of cooling air or loss of motor cooling Attention In the eve...

Страница 9: ...orce for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transported near or on to Store the fans i...

Отзывы: