VertX V100 (CS) Quick Installation Guide
August 2005
Page 3 of 9
2005 © HID Corporation. All rights reserved.
Introduction
VertX™ CS is the first family of access controllers designed specifically for alarm dealers for direct
connection to central stations. Because it was designed with central station in mind, VertX CS works with
software from leading central station automation providers, including Bold Technologies, DICE and
GE MAS.
The V100 is designed to be controlled by a VertX V1000 Access Controller that will also manage
communications with the central station automated software. The V100 Door/Reader Interface panel
controls two sets of door devices or one door with Card In/Card Out (a reader on both sides of the same
door.)
Parts List (included)
Parts List (included)
Quantity
VertX™ V100 Door/Reader Interface
Note:
The V100 panel has a plastic base
and is covered with a Plastic or Mylar cover.
1
Mounting screws
4
2.2K EOL resistors
4
Quick Installation Guide
1
Installation Wiring Diagram Example
1
Note:
A VertX V1000 Access Controller is required.
Product Specifications
Description
Specification
Power Supply
12-16VDC
Maximum current at 12VDC per V100
1 Amp
Average operating current at 12VDC
450mA (with two R40
iCLASS
Readers)
Operating temperature range
32°-122°F (0°-50°C)
Humidity
5% to 95% non-condensing
Cable Specifications
Cable Type
Length
Specification
RS-485 *
4000 feet (1220 m) to V1000
Belden 3105A, 22AWG twisted pair, shielded 100
Ω
cable, or equivalent.
Input Circuits *
500 feet (150 m)
2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C
(18AWG), or equivalent.
Output Circuits *
500 feet (150 m)
2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG), or
equivalent.
Wiegand
500 feet (150 m) to reader
ALPHA 1299C, 22AWG, 9-conductor, stranded, overall shield.
Fewer conductors needed if all control lines are not used.
Power Supply
+12 VDC IN
----
Refer to your Power Supply Installation Guide.
* Minimum wire gauge depends on cable length and current requirements.