background image

The LP4502 is for use in low voltage, Class 2 Circuits only

The installation of this device must comply with all local fire and electrical codes.

Primary power

12 to 24 V DC ± 10 %, 550 mA maximum (reader and USB current not included)

Reader ports

600 mA maximum (add 600 mA to primary power current)

Micro USB port

5 V DC, 500 mA maximum (add 270 mA to primary power current)

Memory and clock backup 
battery

3 Volt Lithium, type BR2330 or CR2330

microSD card

Format: microSD or microSDHC; 2GB to 8GB.

Host communication

Ethernet: 10Base T/100Base-TX and micro USB port (2.0) with optional adapter: 
pluggable model USB2-OTGE100

Serial I/O device

Two each: 2-wire RS-485, 2,400 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 8 
data bits, and 1 stop bit

Inputs

Eight unsupervised/supervised, standard EOL: 1k/1k

Ω

, 1%, ¼ watt

Two unsupervised dedicated for cabinet tamper and UPS fault monitoring

Output

Four relays, Form-C with dry contacts

Normally open contact (NO): 5 A @ 30 V DC resistive

Normally closed contact (NC): 3 A @ 30 V DC resistive

 

Reader interface

Power
(jumper selectable)

12 V DC ± 10% regulated, 300 mA maximum each reader
(input voltage (VIN) must be greater than 20 V DC)

or

12 to 24 V DC ± 10% (input voltage (VIN) passed through), 300 mA maximum each 
reader

Data inputs

TTL compatible, F/2F or 2-wire RS-485

RS-485 mode

9,600 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and 1 stop bit.  
Maximum cable length: 2000 ft. (609.6 m)

LED output

TTL levels, high>3 V, Low<0.5 V, 5 mA source/sink maximum

Buzzer output

Open collector, 12 V DC open circuit maximum, 40 mA sink maximum

 

Cable requirements

Power and relays

1 twisted pair, 18 to 16 AWG

Ethernet

CAT-5, minimum

Reader data (TTL)

6-conductor, 18 AWG, 500 feet (150 m) maximum

Reader data (F/2F)

4-conductor, 18 AWG, 500 feet (150 m) maximum

Reader data (RS-485)

1 twisted pair, shielded.  24 AWG, 120

Ω

 impedance, 2,000 feet (610 m) maximum

RS-485 I/O devices

1 twisted pair, shield.  120

Ω

 impedance, 24 AWG, 4,000 ft. (1,219 m) maximum

Alarm input

1 twisted pair, 30

Ω

 maximum, typically 22 AWG @ 1000 ft. (304.8 m)

 

PLT-05246, A.4

20

June 2021

Powering

Trusted Identities

HID Mercury™ LP4502 Controller

Installation and Specifications

Содержание Mercury LP4502

Страница 1: ...HID Mercury LP4502 Controller Installation and Specifications PLT 05246 A 4 June 2021 HID Mercury LP4502 Controller Installation and Specifications Powering Trusted Identities...

Страница 2: ...chnical Support www hidglobal com support Americas and Corporate Asia Pacific 611 Center Ridge Drive Austin TX 78753 USA Phone 1 866 607 7339 19 F 625 King s Road North Point Island East Hong Kong Pho...

Страница 3: ...Section 01 Powering Trusted Identities Overview...

Страница 4: ...he LP4502 Each reader port can accommodate a read head that utilizes TTL D1 D0 Clock Data F 2F or 2 wire RS 485 electrical signaling OSDP reader for example and also provides tri state LED control and...

Страница 5: ...1 2 LP4502 hardware PLT 05246 A 4 5 June 2021 Powering Trusted Identities HID Mercury LP4502 Controller Installation and Specifications...

Страница 6: ...Section 02 Powering Trusted Identities LP4502 wiring and setup...

Страница 7: ...B 1 TB3 1 GND SIO port 2 2 wire RS 485 TB3 2 TR A 1 TB3 3 TR B 1 TB4 1 IN2 Input 2 TB4 2 IN2 TB4 3 IN1 Input 1 TB4 4 IN1 TB5 1 IN4 Input 4 TB5 2 IN4 TB5 3 IN3 Input 3 TB5 4 IN3 TB6 1 IN6 Input 6 TB6 2...

Страница 8: ...O Out 1 Normally open contact TB10 2 C Out 1 Common TB10 3 NC Out 1 Normally closed contact TB10 4 NO Out 2 Normally open contact TB10 5 C Out 2 Common contact TB10 6 NC Out 2 Normally closed contact...

Страница 9: ...D card J9 OFF Port 1 RS 485 EOL terminator is OFF ON Port 1 RS 485 EOL terminator is ON J10 1 N A Remote Status LED 1 1 J10 2 N A Remote Status LED 2 1 J10 3 N A Remote Status LED 3 1 J10 4 N A Remote...

Страница 10: ...OFF Bulk Erase prompt mode at power up See Bulk erase configuration memory X X X ON Makes the LP4502 report and function like an EP4502 To be used in situations where the host software has not been up...

Страница 11: ...D 1 is on for about 15 seconds while LP4502 boots up 3 Change DIP switches 1 or 2 to OFF Within 10 seconds after LEDs 1 and 2 and LEDs 3 and 4 start flashing alternately at a rate of 0 5 seconds If th...

Страница 12: ...he host via the on board Ethernet 10 BaseT 100Base TX port and or the Micro USB port 2 0 with an optional Micro USB to Ethernet adapter The serial I O device communication ports TB2 for port 1 and TB3...

Страница 13: ...485 signaling requires two 2 conductor cables Use one cable for power 18 AWG 1 pair and one cable for communication 24 AWG 1 pair shielded Note For OSDP cable lengths greater than 200 ft 61 m or EMF...

Страница 14: ...er 2 OSDP installation Typical reader 2 Wiegand or Clock Data installation Typical unsupervised F 2F reader Typical supervised F 2F reader Jumper D1 to LED on supervised F 2F reader PLT 05246 A 4 14 J...

Страница 15: ...voltage A supervised input circuit requires two resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1k 1 resistors and should be located as close...

Страница 16: ...ded that a diode is used to protect the relay Wire should be of sufficient gauge to avoid voltage loss Diode selection n Diode current rating 1x strike current n Diode breakdown voltage 4x strike volt...

Страница 17: ...On line 80 ON Double flash if battery is low 2 Host communication activity Ethernet 3 Internal SIO communication activity 4 External SIO communication activity Port 1 5 External SIO communication act...

Страница 18: ...ith a default login account which is enabled when DIP 1 is moved from OFF to ON See DIP switches The default login user name admin and password password will be available for five minutes once the DIP...

Страница 19: ...Section 03 Powering Trusted Identities Specifications...

Страница 20: ...ormally closed contact NC 3 A 30 V DC resistive Reader interface Power jumper selectable 12 V DC 10 regulated 300 mA maximum each reader input voltage VIN must be greater than 20 V DC or 12 to 24 V DC...

Страница 21: ...rranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Autho...

Страница 22: ...t table in 2 6 Reader wiring A 3 February 2021 Correction to LP4502 connections A 2 January 2021 Add J19 Battery backup call out to the hardware diagram A 1 October 2020 Initial release A 0 PLT 05246...

Страница 23: ...a Pacific 19 F 625 King s Road North Point Island East Hong Kong Europe Middle East Africa 3 Cae Gwyrdd Green Meadow Springs Cardiff CF15 7AB United Kingdom Brazil Condom nio Business Center Av Ermano...

Отзывы: