The interface is for use in low voltage, Class 2 Circuits only.

The installation of this device must comply with all local fire and electrical codes.

Primary power

12 to 24 V DC ± 10%, 500 mA maximum (reader and USB ports not included)

Reader ports

600 mA maximum (add 600 mA to primary power current)

Micro USB port

5 V DC, 500 mA maximum (add 270 mA to primary power current)

Memory and clock backup 
battery

3 Volt Lithium, type BR2330 or CR2330

microSD card

Format: microSD or microSDHC; 2GB to 8GB

Host communication

Ethernet: 10-BaseT/100Base-TX and Micro USB port (2.0) with optional adapter: 
pluggable model USB2-OTGE100

Serial I/O device

One each: 2-wire RS-485, 2,400 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 
8 data bits, and 1 stop bit

Inputs

Eight unsupervised/supervised, standard EOL: 1k/1k

Ω

, 1%, ¼ watt

Two unsupervised dedicated for cabinet tamper and UPS fault monitoring

Outputs

Four relays, Form-C with dry contacts

Normally open contact (NO) contact: 5 A @ 30 V DC resistive

Normally closed contact (NC) contact: 3 A @ 30 V DC resistive

 

Reader interface

Power
(jumper selectable)

12 V DC ± 10% regulated, 300 mA maximum each reader
(input voltage (VIN) must be greater than 20 V DC)

or

12 to 24 V DC ±10 % (input voltage (VIN) passed through), 300 mA maximum each 
reader

Data inputs

TTL compatible, F/2F or 2-wire RS-485

RS-485 Mode

9,600 to 115,200 bps, asynchronous, half-duplex, 1 start bit, 8 data bits, and 1 stop bit.  
Maximum cable length: 2000 feet. (609.6 m)

LED output

TTL levels, high>3 V, low<0.5 V, 5 mA source/sink maximum

Buzzer output

Open collector, 12 V DC open circuit maximum, 40 mA sink maximum

 

Cable requirements

Power and relays

1 twisted pair, 18 to 16 AWG

Ethernet

CAT-5, minimum

RS-485

I/O Device port

1 twisted pair, shielded, 120

Ω

 impedance, 24 AWG, 4,000 feet. (1,219 m) max.

Reader port

1 twisted pair, shielded, 120

Ω

 impedance, 24 AWG, 2,000 feet. (610 m) max.

Alarm input

1 twisted pair, 30

Ω

 maximum

  

PLT-05244, A.3

19

June 2021

Powering

Trusted Identities

HID Mercury™ LP1502 Controller

Installation and Specifications

Содержание Mercury LP1502

Страница 1: ...HID Mercury LP1502 Controller Installation and Specifications PLT 05244 A 3 June 2021 HID Mercury LP1502 Controller Installation and Specifications Powering Trusted Identities...

Страница 2: ...chnical Support www hidglobal com support Americas and Corporate Asia Pacific 611 Center Ridge Drive Austin TX 78753 USA Phone 1 866 607 7339 19 F 625 King s Road North Point Island East Hong Kong Pho...

Страница 3: ...Section 01 Powering Trusted Identities Overview...

Страница 4: ...eader that uses TTL D1 D0 Clock Data F 2F standard or supervised or 2 wire RS 485 device signaling OSDP reader for example and also provides tri state LED control and buzzer control one wire LED mode...

Страница 5: ...Section 02 Powering Trusted Identities LP1502 wiring and setup...

Страница 6: ...t 2 wire RS 485 TB3 2 TR B 1 TB3 3 TR A 1 TB4 1 IN2 Input 2 TB4 2 IN2 TB4 3 IN1 Input 1 TB4 4 IN1 TB5 1 IN4 Input 4 TB5 2 IN4 TB5 3 IN3 Input 3 TB5 4 IN3 TB6 1 IN6 Input 6 TB6 2 IN6 TB6 3 IN5 Input 5...

Страница 7: ...Normally open contact TB10 2 C Out 1 Common contact TB10 3 NC Out 1 Normally closed contact TB10 4 NO Out 2 Normally open contact TB10 5 C Out 2 Common contact TB10 6 NC Out 2 Normally closed contact...

Страница 8: ...eader ports PASS VIN Pass Through to reader ports J8 N A microSD card J10 1 N A Remote Status LED 1 1 J10 2 N A Remote Status LED 2 1 J10 3 N A Remote Status LED 3 1 J10 4 N A Remote Status LED 4 1 J1...

Страница 9: ...FF Bulk Erase prompt mode at power up See Bulk erase configuration memory X X X ON Makes the LP1502 report and function like an EP1502 To be used in situations where the host software has not been upd...

Страница 10: ...D 1 is on for about 15 seconds while LP1502 boots up 3 Change DIP switches 1 or 2 to OFF Within 10 seconds after LEDs 1 and 2 and LEDs 3 and 4 start flashing alternately at a rate of 0 5 seconds If th...

Страница 11: ...g The LP1502 controller communicates with the host via the on board Ethernet 10 BaseT 100Base TX port and or the USB port 2 0 with an optional USB to Ethernet adapter The serial I O device communicati...

Страница 12: ...uires two 2 conductor cables Use one cable for power 18 AWG and one cable for communication 24 AWG with drain wire and shield Note For OSDP cable lengths greater than 200 ft 61 m or EMF interference i...

Страница 13: ...al reader 2 Wiegand or Clock Data installation Typical unsupervised F 2F reader Typical supervised F 2F reader Jumper D1 to LED on supervised F 2F reader Inputs on supervised F 2F readers may be unsup...

Страница 14: ...voltage A supervised input circuit requires two resistors be added to the circuit to facilitate proper reporting The standard supervised circuit requires 1k 1 resistors and should be located as close...

Страница 15: ...a diode is used to protect the relay Wire should be of sufficient gauge to avoid voltage loss Diode selection n Diode current rating 1x strike current n Diode breakdown voltage 4x strike voltage n Fo...

Страница 16: ...battery status Off line 20 ON On line 80 ON Double flash if battery is low 2 Host communication activity Ethernet or Micro USB port 3 Internal SIO communication activity 4 External SIO communication...

Страница 17: ...is shipped from the factory with a default login account which is enabled when DIP 1 is moved from OFF to ON See DIP switches The default login user name admin and password password will be available...

Страница 18: ...Section 03 Powering Trusted Identities Specifications...

Страница 19: ...rm C with dry contacts Normally open contact NO contact 5 A 30 V DC resistive Normally closed contact NC contact 3 A 30 V DC resistive Reader interface Power jumper selectable 12 V DC 10 regulated 300...

Страница 20: ...anties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returns must be accompanied by a Return Material Authori...

Страница 21: ...Added reader power select table in 2 7 Reader wiring A 2 January 2021 Add J19 Battery backup call out to the hardware diagram A 1 October 2020 Initial release A 0 PLT 05244 A 3 21 June 2021 Powering...

Страница 22: ...a Pacific 19 F 625 King s Road North Point Island East Hong Kong Europe Middle East Africa 3 Cae Gwyrdd Green Meadow Springs Cardiff CF15 7AB United Kingdom Brazil Condom nio Business Center Av Ermano...

Отзывы: