background image

www.hi-velocity.com

© 1995-2013 Energy Saving Products Ltd.

Troubleshooting the TXV

When  issues  arise  that  bring  the  function  of  the  TXV  into 

question, factors must be looked into before replacement. Inspect 

the  TXV  for  signs  of  damage.  This  may  be  from  a  pinched 

equalizer line to a burnt valve. These issues will have an adverse 

affect on the operation of the valve. Should the equalizer line be 

pinched, the valve will no longer be able to supply the proper 

amount  of  refrigerant  to  the  coil. A  burnt  valve  may  have  an 

effect on the refrigerant charge of the TXV bulb or the seal of the 

valve. This may again cause an improper amount of refrigerant 

to be metered by the valve or cause the valve head to become 

seized. 

The TXV bulb location and mounting should also be inspected. 

The  bulb  should  be  securely  mounted  on  the  top  half  of  the 

suction line. If the bulb is loose or on the lower half of the line, 

the bulb will not properly sense the refrigerant temperature and 

will not meter the proper amount of refrigerant. Ensure that the 

bulb is also properly insulated, as a lack of insulation will expose 

the bulb to conditions well outside those of the coil. This will 

cause an overfeed of refrigerant to the system.

Should the installation of the valve be proper, and no damage 

is evident, inspect the operation of the valve. If the TXV bulb 

is  removed  and  held  in  ones  hand,  the  valve  should  react 

accordingly. This sudden increase in heat will open the valve. 

This will cause a rise in suction pressure and a drop in liquid 

pressure. Should nothing happen, the valve is likely seized and 

will need to be replaced.

Specifications

RPM-E-50

RPM-E-70

RPM-E-100

Matching Fan Coil

HE-Z/HE/HV - 50 / 51 / 52

LV-50

HE-Z/HE/HV - 70 / 71

LV-70

HE-Z/HE/HV - 100 / 101

LV-120/140

Part Number

20090200050

20090200070

20090200100

Refrigerant Type

R-410A

R-410A

R-410A

TX Cooling MBH

   

18-24 

(5.3-7.0 kW)

30-36 

(8.8-10.6 kW)

42-60 

(12.3-17.6 kW)

Latent Cooling MBH

6.8-8.9 

(2.0-2.6 kW)

11.7-13.7 

(3.4-4.0 kW)

16.0-22.2 

(4.7-6.5 kW)

Fin Material

Aluminum

Aluminum

Aluminum

Tubing Material

Copper

Copper

Copper

Type of Fins

.006 Al

.006 Al

.006 Al

Connection Sizes

Liquid Line (Lq)

3/8” 

(9.5mm)

3/8” 

(9.5mm)

3/8” 

(9.5mm)

Suction Line (S)

7/8” 

(22.3mm)

7/8” 

(22.3mm)

7/8” 

(22.3mm)

Drain Connection

3/4” 

(19mm)

3/4” 

(19mm)

3/4” 

(19mm)

TXV with Built in Check Valve & Bypass

Yes

Yes

Yes

Site Glass

Yes

Yes

Yes

Access Ports

Yes

Yes

Yes

Freeze Stat

Yes

Yes

Yes

Shipping Weight (lbs)

48 

(22kg)

59 

(27kg)

74 

(34kg)

Module Size (L x W x H)

19

1⁄4

” x 14

5⁄8

” x 18

1⁄2

(489mm x 371mm x 470mm)

24

1⁄4

” x 14

5⁄8

” x 18

1⁄2

(616mm x 371mm x 470mm)

32” x 14

5⁄8

” x 18

1⁄2

” 

(813mm x 371mm x 470mm)

Tons

2

1.5 - 2.0 

(5.3 - 7.0 Kw)

2.5 - 3.0 

(8.8 - 10.6 Kw)

3.5 - 5.0 

(12.3 - 17.6 Kw)

1) Smaller condensers may be matched to the fan coil when needed (match TXV to condenser size)

MBH = Thousand British Thermal Units per Hour

TX = Thermal Expansion

TXV = Thermal Expansion Valve

2) Minimum of 8 full 2” (51mm) outlets per ton of cooling needed (4 outlets for HE)

and outdoor unit, on and off. This often takes the form of very 

short and frequent on cycles. There are many factors that may 

contribute to short cycling of the refrigerant system. These issues 

can  generally  be  broken  down  between  airflow  related  issues, 

refrigerant issues, and installation issues.

Low airflow rates are one of the most common causes of short 

cycling. As the airflow rate is lowered across the cooling coil, 

the coil pressure drops along with it. This lowers the temperature 

of the coil and may cause the freeze-stat to trip. As the system 

settles, the freeze-stat closes and the cycle begins again, as the 

unit does not run long enough for the space to become adequately 

conditioned. Ensure that the proper amount of airflow is provided 

to the coil. Check for proper air flows and return air practices.

Improperly charged systems run the risk of short cycling as 

well. An  undercharged  system  will  react  much  the  same  as  a 

system with low airflow. If the charge is low enough, it may trip 

out on low pressure. If a system is overcharged, it may trip out on 

high head pressure. Ensure that the system charge is within the 

bounds described in section “Piping the RPM-E”.

System  set-up  and  installation  should  be  checked  as  well. 

Piping practices should be within the bounds described in section 

“Piping the RPM-E” and within the realms of the outdoor unit 

manufacturer. Extreme and often unnecessary adjustment of the 

TXV  can  create  conditions  similar  to  an  undercharged  coil. A 

poorly placed T-stat, such as underneath a vent, can cause short 

cycling.  This  happens  due  to  the  T-stat  being  satisfied  very 

shortly after the unit has begun to operate.

Module RPM

Refrigerant Module Installation (RPM-E) (5/5)

Short Cycling

Short cycling is the unnecessary running of the indoor

Module RPM Refrigerant Module Installation (RPM-E) (5/5)

 

Содержание RPM-E Series

Страница 1: ...Small Duct Heating Cooling and Indoor Air Quality Systems Hi Velocity Systems RPM E Cooling Installation Module RPM RPM E Cooling Installation 052813 www hi velocity com www hi velocity com Manufactured By ...

Страница 2: ...access hatch The liquid and suction lines have male solder connections at a standard width making connections to the condenser lines quick and easy Fig RPM 01 RPM E Cooling Module Configurations When installing follow the recommendations shown in Table 01 demonstrated in Fig 01 For example a horizontal application could use A to B while highboy applications could use A to B1 Do not use a combinati...

Страница 3: ... with a 19mm primary and secondary outlet The condensate drain must have a vented p trap installed Fig RPM 05 and run at a slope of 6 7mm per foot in the direction of the drain When installing the P trap one must be installed on both the primary and secondary outlets The P traps must have a minimum depth of two inches 51mm Due to the high negative pressure of the blower system the RPM E will hold ...

Страница 4: ...heat dissipating paste to ensure no overheating occurs to the pre piped coil assembly Excess heat may damage the RPM E components Fig RPM 06 Remove Front Access Panel Once the system has been brazed it must be pressure tested Pressure testing must be done with nitrogen and not refrigerant Typically pressures are tested to the maximum operating pressure that the system will see Allow the system to ...

Страница 5: ...airflow rates of SDHV systems The RPM E coil can operate at a level that is different from most other conventional system coils Typically superheat level are low two to four degrees of superheat Adjustment of the valve also differs somewhat Rather than having a large effect on the range of superheat adjustment of the valve has a larger effect on the system pressures superheat maintaining a fairly ...

Страница 6: ...h Built in Check Valve Bypass Yes Yes Yes Site Glass Yes Yes Yes Access Ports Yes Yes Yes Freeze Stat Yes Yes Yes Shipping Weight lbs 48 22kg 59 27kg 74 34kg Module Size L x W x H 191 4 x 145 8 x 181 2 489mm x 371mm x 470mm 241 4 x 145 8 x 181 2 616mm x 371mm x 470mm 32 x 145 8 x 181 2 813mm x 371mm x 470mm Tons2 1 5 2 0 5 3 7 0 Kw 2 5 3 0 8 8 10 6 Kw 3 5 5 0 12 3 17 6 Kw 1 Smaller condensers may ...

Отзывы:

Похожие инструкции для RPM-E Series