background image

www.hi-velocity.com

© 1995-2009 Energy Saving Products Ltd.

*IMPORTANT:  The freeze control serves the

purpose of preventing severe icing of the coil in the 

event of an undercharge or low load on the coil. This 

piece of equipment must be used at all times. Lack 

of use of the freeze-stat will result in RPM-E related 

warranty issues being voided.

A

A1

B

B1

COIL

Module RPM

Refrigerant Module Installation (RPM-E) (1/5)

Rough Opening Sizes

A or B

A1 or B1

RPM-E 50

11

3/4

”L X 13

1/4

”H 

(298mm X 337mm)

11

3/4

”L X 9”W

(298mm X 229mm)

RPM-E-70

16

3/4

”L X 13

1/4

”H

(425mm X 337mm)

16

3/4

”L X 9”W

(425mm X 229mm)

RPM-E-100

22

3/4

”L X 13

1/4

”H

(578mm X 337mm)

22

3/4

”L X 9”W

(578mm X 229mm)

Module RPM Refrigerant Module Installation (RPM-E) (1/5)

Refrigerant Modules (RPM-E)

The RPM-E series cooling module can be used with the Hi-

Velocity Fancoil, installed in many different positions. It is pre-

piped with an adjustable, heat pump ready, thermal expansion 

valve and comes with a bleed port, sight glass, suction and liquid 

line access ports, freeze-stat, and two L brackets for mounting.

The RPM-E comes as a complete module and must be installed 

in the vertical position on the return air side of the fancoil; the 

unit cannot be turned on its side and is a draw through unit 

only. The  module  offers  multi-position  airflow  configurations 

for  horizontal,  highboy,  or  counter-flow  configurations.

 (Fig. 

RPM-01)

The TXV (Thermal Expansion Valve), sight glass, access 

ports, and freeze-stat* are already installed and are accessible 

through an easy to remove access hatch. The liquid and suction 

lines have male solder connections at a standard width making 

connections to the condenser lines quick and easy. 

Fig. RPM-01 - RPM-E Cooling Module Configurations

When installing, follow the recommendations shown in 

Table 01, demonstrated in Fig. 01. For example, a horizontal 

application could use A to B while highboy applications could 

use A to B1. Do not use a combination of A to A1 or B to B1, 

as this would bypass the cooling coil completely. A1 is not 

to be used for outlet airflow. The knock-outs can be removed 

with a screw driver and hammer. Use caution when opening 

the knock-outs, ensuring you do not damage the coil surface.

Configurations

*B to A and B1 to A configurations are not recommended,

due to a higher chance of carry-over issues. 
Important:  If side A1 is going to be used in your selected 

configuration, the extended drain pan must be removed.

RPM-E Drain Pan Extension

The RPM-E Drain Pan Extension (DPE) is to be removed for 

up flow (vertical) return air applications (avoid installing the 

RPM-E in counter flow applications). 

The lower knockout can now be removed, using a screwdriver 

and hammer 

(Fig-RPM-03).

 Use caution when removing 

knockouts ensuring you do not damage the coil inside the 

module. 

To remove the pre-installed DPE, first remove left side access 

panel of the RPM-E Module.  Remove the 3 - ¼ ”  screws 

that hold the DPE in place, remove the DPE and replace ¼” 

screws into the coil support 

(Fig. RPM-02).

 Replace the left 

side access panel.

Right

Wrong

A to B

B1 to A1

A to B1

B to A1

A1 to B

A to A1

A1 to B1

B to B1

B to A*

B1 to A*

Table RPM-01 - RPM-E Cooling Module Configurations

Fig-RPM-02 - Remove DPE

Fig-RPM-03 - Remove Knockout

© 1995-2013 Energy Saving Products Ltd.

Содержание RPM-E Series

Страница 1: ...Small Duct Heating Cooling and Indoor Air Quality Systems Hi Velocity Systems RPM E Cooling Installation Module RPM RPM E Cooling Installation 052813 www hi velocity com www hi velocity com Manufactured By ...

Страница 2: ...access hatch The liquid and suction lines have male solder connections at a standard width making connections to the condenser lines quick and easy Fig RPM 01 RPM E Cooling Module Configurations When installing follow the recommendations shown in Table 01 demonstrated in Fig 01 For example a horizontal application could use A to B while highboy applications could use A to B1 Do not use a combinati...

Страница 3: ... with a 19mm primary and secondary outlet The condensate drain must have a vented p trap installed Fig RPM 05 and run at a slope of 6 7mm per foot in the direction of the drain When installing the P trap one must be installed on both the primary and secondary outlets The P traps must have a minimum depth of two inches 51mm Due to the high negative pressure of the blower system the RPM E will hold ...

Страница 4: ...heat dissipating paste to ensure no overheating occurs to the pre piped coil assembly Excess heat may damage the RPM E components Fig RPM 06 Remove Front Access Panel Once the system has been brazed it must be pressure tested Pressure testing must be done with nitrogen and not refrigerant Typically pressures are tested to the maximum operating pressure that the system will see Allow the system to ...

Страница 5: ...airflow rates of SDHV systems The RPM E coil can operate at a level that is different from most other conventional system coils Typically superheat level are low two to four degrees of superheat Adjustment of the valve also differs somewhat Rather than having a large effect on the range of superheat adjustment of the valve has a larger effect on the system pressures superheat maintaining a fairly ...

Страница 6: ...h Built in Check Valve Bypass Yes Yes Yes Site Glass Yes Yes Yes Access Ports Yes Yes Yes Freeze Stat Yes Yes Yes Shipping Weight lbs 48 22kg 59 27kg 74 34kg Module Size L x W x H 191 4 x 145 8 x 181 2 489mm x 371mm x 470mm 241 4 x 145 8 x 181 2 616mm x 371mm x 470mm 32 x 145 8 x 181 2 813mm x 371mm x 470mm Tons2 1 5 2 0 5 3 7 0 Kw 2 5 3 0 8 8 10 6 Kw 3 5 5 0 12 3 17 6 Kw 1 Smaller condensers may ...

Отзывы: