background image

F.000

Open and Closed Adjustment Stops

The 

Adjustment Stops

 can be 

adjusted to stop rotating before it 
reaches its stops. These can be 
moved to any position without harm.
1. Loosen the end stops. 

Caution: be 

cautious not to unscrew from the 
captive nut under the slot.

2. Move the stops (2.5° steps) to the 

desired position and re-tighten the 
screw.

Manual Override Button

 

Press the 

Manual Override Button

 

and the gear train is dis-engaged so 
the damper shaft can be moved 
manually. Release the button and the 
gear train is re-engaged.

To lock in manual mode press down 
the Manual Override Button and push 
in the side locking tab. To release, 
push down the Manual Override 
Button and release this will disengage 
lock.

0

1

0

1

Manual Override

Button

1

-

~

+

2

~

3+

Closing and Opening

Adjustment Stops

M6 - 24vac Closes damper
M4 - 24vac Opens damper
M2 - Constant 24 vac HOT
M1 - Common 24 vac

ZONE DAMPER WIRING

M6
M4
M2
M1

3
2

1

Constant Fan Comfort

Having the fan switch at the thermostat to the 
“ON” position is strongly recommended. This 
utilizes continuous air circulation for optimal 
Indoor Air Quality (IAQ) and Energy Efficiency. 
Independent testing has shown that utilizing the 
recirculating fan with the Hi-Velocity Systems 
VFD motor reduces total energy usage. This is 
due to less on/off cycling of AC and Heating 
equipment by constant de-stratification of the air.

The zone controller board will default the 
actuators in the open position when there is no 
call for constant fan, heat or cooling. If one of the 
zones is calling for constant fan and the others 
are not, the zones that are not calling will close. 

In the event of a zone calling for heat or cooling 
the zone dampers (regardless if a zone is calling 
for constant fan) will close the non-calling 
heat/cool zones.  The actuators have been pre-
adjusted with approximately 10% bleed through, 
this allows for air to circulate in a non-calling 
zone. With the 10% by-pass it will not over heat 
or cool a non-calling zone if the other zones are 
calling heat or cooling but will add comfort as the 
air will not be stagnate in the non-calling zone 
and will supply more even air temperatures 
throughout. 

Zone Dampers Adjustment Stops

The 

Adjustment Stops

 on the 

actuators have been preadjusted with 
approximately 10% bleed through. 
This allows for air to circulate in a 
non-calling zone. This can be 
adjusted by adjusting the “0" stop 
limit.

Balancing Zones

In the case that there is too much 
pressure through a calling zone 
(usually a smaller zone on the 
system) the damper can be adjusted 
partially closed. Partially closing a 
damper will cause back pressure on 
the blowers pressure control and the 
fan coil will slow down the motor. 
Adjust the “1" stop to limit the 
actuators opening to the level of 
pressure/air required for the air flow 
desired for the smaller zone. 

Zone damper Wiring

The zone dampers on the HE-Z 
Zoning Fan Coil comes pre-wired. 
There are 

Seven Built-in Timers that 

over ride the operation of the zone 
dampers and output signals of the 
zone board these are shown on 
pages 2 and 3.

Damper Adjustment

6

052917

Pre-Release 052917

Содержание HE-Z

Страница 1: ...cool Automatic Heat Cool Changeover Automatic changeover from any thermostat allowing for individual zone comfort Status LED A green STATUS LED pulses as a steady heart beat to indicate Micro processor activity and 24v power is present System LEDs Function specific colored LED s illuminate to indicate the HVAC system mode of operation and active zone identification Damper LEDs Green LEDs labelled ...

Страница 2: ...C Start up Delay Timer 3 minutes fixed Short Cycle Timer 3 minutes fixed Change Over Timer 4 minutes fixed Opposing Call Timer 20 minutes fixed Staging Timer OFF or 7 42 min Adj Supply Air Limit Timer 3 minutes fixed Purge Delay Timer 90 seconds fixed Programming and Setting up your HVAC System Review each pin setting explanation of each dip switch function and choose your settings for correct ope...

Страница 3: ...at to indicate proper Micro processor system status The OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen set point The OAS LED will blink rapidly to indicate a shorted or open Outdoor Air Sensor circuit The SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen set point on either the HIGH TEMP LIMIT or the LOW TEMP L...

Страница 4: ... SWITCH GAS FAN HYDRONIC OFF SAS ON OFF 50 RULE ON OAS STAGING TIMER HC TSTATS HP HP SYSTEM OTHER DF SYSTEM CONV TIMER OAS STAGING 42 35 28 21 14 7 OFF R1 OFF 7 42 minutes or 7 42 degrees F Any Setting below 7 is OFF OFF DO NOT set to OFF when using OAS Emergency Heat Switch Isolated HVAC System Terminal Block Future Supply Air and Outdoor Air Sensor Connections 24v 4 0 amp Fuse STAGING TIMER W2 E...

Страница 5: ...kage includes pre wired zone panel and 2 3 or 4 collars each w power open close dampers and actuators installed These are currently available pre installed on our HE Z Series Fan Coils Order HE Z fan coil unit from our Standard Price List and add these multi outlet tops to your order as a separate part The plenum take off outlets are 7 in height and adds to the height of the 32 fan coil The fan co...

Страница 6: ...is no call for constant fan heat or cooling If one of the zones is calling for constant fan and the others are not the zones that are not calling will close In the event of a zone calling for heat or cooling the zone dampers regardless if a zone is calling for constant fan will close the non calling heat cool zones The actuators have been pre adjusted with approximately 10 bleed through this allow...

Страница 7: ...UT ZONE 2 THERMOSTAT G R O B Y W E C C W Y R G O B ZONE 2 THERMOSTAT INPUT 3 2 1 M6 M4 M2 M1 ZONE 2 DAMPER 3 2 1 M6 M4 M2 M1 ZONE 3 DAMPER 3 2 1 M6 M4 M2 M1 ZONE 1 DAMPER 24V INPUT 4 0A PROTECTED R C R C G Y2 Y1 O W1 B W2 E RH RC C ZONE 1 THERMOSTAT C W Y R G O B ZONE 1 THERMOSTAT INPUT G R O B Y W E C ONE ZONE HVAC SYSTEM HI VELOCITY PSB CIRCUIT BOARD Dampers default to the OPEN position After a ...

Страница 8: ... B G R Y1 W2 W1 FZ FZ Y2 C F1 AUXILIARY RELAY HEATING L L L2 L2 N L1 L1 A3 A2 A1 L N COOL HEAT FAN LED L1 J8 ON OFF H2 TIMER AUTO MAN H3 MODE ON OFF H4 DELAY J5 J7 J4 U2 J3 R8 R7 R6 G C H F 318 29 Pcbw 001sep 040 J2 N C Ri Ro H1 J9 J1 LED L2 PSB CIRCUIT BOARD 24v OUTPUT EMERGENCY DISCONNECT C 110 127 VAC 110 127 1 50 60 110 127v POWER CABLE L N Ground WH BK G LINE IN EMERGENCY DISCONNECT C 24 VAC ...

Страница 9: ...LAY J5 J7 J4 U2 J3 R8 R7 R6 G C H F 318 29 Pcbw 001sep 040 J2 N C Ri Ro H1 J9 J1 LED L2 PSB CIRCUIT BOARD 24v OUTPUT EMERGENCY DISCONNECT C 1 2 3 4 5 6 7 8 9 10 11 12 L L1 N L2 U V W PE P 0 I Parameter Value WEG CONTROLLER VFD 200 240 VAC MOTOR LEADS PLUG 3 PHASE CAUTION FOR SINGLE STAGE COOLING OPERATION USE Y2 OTHERWISE THE FREEZE STAT WILL BE BYPASSED CAUTION FOR SINGLE STAGE COOLING OPERATION ...

Страница 10: ... TERMINAL 4 AUXILIARY HEATING RELAY TIMER ACTIVATES CIRCUIT FOR 5 MINUTES EVERY 24 HOURS STARTING WHEN POWER IS APPLIED TO THE UNIT 5 LED 1 INDICATOR LIGHT FOR FAN SPEED OPERATION AND AUXILIARY RELAY OPERATION SEE BELOW FOR LIGHT OPERATION SEQUENCE 6 SEE INSTALLATION MANUAL FOR MORE DETAILED WIRING DIAGRAMS 7 8 FAILURE TO SET PROPER AIR FLOW AND OR OPERATION OF THE SYSTEM MAY RESULT IN DAMAGE TO E...