Section 6
-
Maintenance Harrington Generators International
8kVA Diesel Generator 30 Part No: 498
-
141
8kVA Diesel Generator 30 Part No: 498
-
141
Maintenance Schedule
Kubota
Daily
Checks
After the
first 50
hours
Every 3
months
or
200 hours
Every 6
months
or
400 hours
Every 12
months
or
800 hours
Check & replenish fuel
9
Check & replenish engine oil
9
Check fuel filter for dirt and water
9
Check coolant level
9
Check battery fluid level (if refillable)
9
Check for oil and fuel leaks
9
Check operation of earth leakage
unit (RCD) trip (if fitted).
9
Check the hours run meter works
9
Change engine oil
9
9
Replace oil filter
9
9
Replace fuel filter
9
Check air filter & clean
9
9
9
Replace air filter
9
Adjust valve clearances
9
Replace coolant
9
Check radiator hoses & clamps
9
Check intake air hoses & clamps
9
Replace fan belt
9
Check fan belt tension
9
9
Check operation of MCBs
9
Control Module Safety Shut Down
9
Battery Charger (where fitted)
9
Canopy
9
General Inspections
9
6.1 Service Schedule
Service intervals will have to be reduced if the generator is operated in dusty or severe conditions. The
first service is required after 50 hours from new then as given below.
Servicing must be carried out by a competent engineer. A written record of the service work should be
made using the form contained in this manual or a similar form. The generator must be serviced in ac-
cordance with our recommendations for the warranty to remain valid.
DO NOT use a pressure washer to clean the generator as high pressure water may enter the electrical
system. Use a damp cloth or similar.