LOCATION AND INSTALLATION/VENTILATION
(CONTINUED)
W
V
E
INSTALLATION CLEARANCES 36” WITH LOW BACKGUARD
FRONT VIEW
G
VALVE LOCATION
VENT HOOD
MIN. CLEARANCE
TO NEAREST
COMBUSTIBLE
SIDE SURFACE
COMBUSTIBLE
MATERIALS
12”
[30.5]
2-1/2”
[6.4]
6”
[15.2]
5”
[12.7]
FINISHED
FLOOR
DIMENSIONS IN
BRACKETS [ ] ARE
IN CM.
3”
[7.6]
5”
[12.7]
19”
[48.3]
[24.1]
ELECTRICAL
SUPPLY
LOCATION
18” [45.7]
MIN.
9-1/2”
RECOMMENDED
GAS SHUT-OFF
[45.7]
18”
NOTES:
* SHADED AREAS INDICATE WHERE COMBUSTIBLE MATERIALS ARE NOT ALLOWED.
* APPLIANCE TOP MUST BE LEVEL OR HIGHER THAN THE ADJACENT COUNTERTOP SURFACES.
* "G" IS GAS CONNECTION ZONE ON REAR WALL. MOUNT SHUT-OFF VALVE AS HIGH AS POSSIBLE
IN THIS ZONE FOR EASY ACCESS WHEN RANGE IS INSTALLED.
* "E" IS ELECTRICAL SUPPLY ZONE.
* "W" IS APPLIANCE OPENING.
* "V" IS MIN. CLEARANCE TO REQUIRED VENTILATION HOOD.
RANGE MODEL
W
V
(MIN)
KRD365
36” [91.4]
30” [76.2]
KRD364GD
36” [91.4]
30” [76.2]