Chapter 10 Technical appendix
Device description HE 5697 MFC
43
Version 1.4
Current measurement
10.1.2.3 mV-input
Channel 2 is used to process high-impedance voltage sources.
The input is a differential input.
Voltage measurement
10.1.2.4 Analogue outputs
The I/O card is equipped with two analogue outputs.
These provide one voltage and one current output.
Input type:
Current
Connection type:
2-conductor
Measuring ranges:
0 to 20 mA
Detection range:
Measuring range +/- 10%
Input impedance:
max. 50 Ω
Accuracy:
≤0.1%
Temperature drift:
≤0.08% / 10 K
Measuring circuit monitoring:Detection range - underflow / overflow
Input type:
Voltage
Connection type:
2-conductor
Measuring range:
-200 to 1800 mV
Detection range:
Measuring range +/- 10%
Input impedance:
max. 150 MΩ
Accuracy:
≤0.1%
Temperaturdrift:
≤0.08% / 10 K
Measuring circuit monitoring:Detection range - underflow / overflow
Converter resolution:
12 Bit
Linearity:
<0.1%
Accuracy:
<0.2%
Temperature drift:
≤0.1% / 10K
Cycle time:
50 ms
Galvanic isolation: