HE 5422 Operating Instructions
# 342338 | Version 1.3
41
11
Error messages
Display / LED
Cause
Remedy
The differential pressure
display flashes:
EEPROM parameter error
Restore factory
settings and check
parameterization.
If this is not
successful, send the
device to HESCH for
repair.
The differential pressure
display shows:
The differential pressure signal is
below the permissible measuring
range.
Check differential
pressure signal.
Check external
threaded connection.
The differential pressure
display shows:
The differential pressure signal is
above the permissible measuring
range.
Check differential
pressure signal.
Check external
threaded connection.
The differential pressure
display shows:
and the high and low
alarm LEDs flash
alternately
Fault in
Δp-module.
The yellow status LED on the
p
module does not light up.
p module is not inserted or not
firmly seated on the PCB.
Insert the
p module
or check and correct
the fit.
If the status LED still
does not light up,
please contact
HESCH service (
see
chapter 12
Maintenance and
Service
The high alarm LED
flashes:
The differential pressure exceeds
the set threshold.
Adjust the configured
pulse and pause
times.
Check filter element.
Check the solenoid
valves for optimal
mechanical function.
Check the
compressed air
system.
The low alarm LED
flashes:
The differential pressure falls
below the set threshold for more
than 5 minutes without reaching
the post-cleaning threshold.
Adjust the configured
pulse and pause
times.