HE 5411 Operating Instructions
#340411 | version 1.7
Parameter
Adjustment range
Factory Setting
Unit
Display / Output
Creep flow suppression
Flattens the output signal
after root extraction at
small differential pressures
(around zero).
Functionalities:
None
(function is deactivated)
Step
(the
parameter ‘creep flow
threshold
’ defines the
range around zero. Within
this range, the displayed
value and the output signal
are set to zero,
see Figure
. Is mostly used when
the volume flow is
subsequently added up.)
Linear
(the
parameter ‘creep flow
threshold’ defines the
range around zero. Within
this range, the square
rooted characteristic line is
replaced by a linear one =>
increase around zero is
limited,
Mostly used for
downstream controls.)
None, step, linear
Step
Creep flow threshold
Min. = Display value start
Max. = Display value end
Min.…Max.
10% from Max.
Unit
The unit you wish to be displayed
can be set with this parameter.
mbar, Pa, inH2O,
psi,
Display value start
-
999.00…9999.00
0.0
Display value end
-
999.00…9999.00
100.0
Upper limit value
This parameter can also be
set on the device itself.
See chapter 7.1
Sensor
Min…Sensor Max,
Off
75% of
basic measuring range end
mbar, Pa,
inH2O, psi
Upper hysteresis limit value
See chapter 7.1
1% of
basic measuring range end