26
HE 5411 Operating Instructions
#340411 | version 1.7
8.4
Analogue Output Setting
1.
The analogue output can be selected between 0…20 mA or
4…20 mA with the slide switch.
•
0…20 mA (left)
•
4…20 mA (right)
8.5
Setting the measuring range
The measuring range is set with the rotary coding switch.
The different spreads depend on the full measuring range of the
sensor used.
The following table shows the measuring ranges which can be configured.
Rotary coding switch
position
Measurement range
Display
0
Set with the PC tool
1
100 % bidirectional
pressure
2
80 % bidirectional
pressure
3
50 % bidirectional
pressure
4
100 % unidirectional
pressure
5
80 % unidirectional
pressure
6
50 % unidirectional
pressure
7
100 % bidirectional, square rooted
%
8
80 % bidirectional, square rooted
%
9
50 % bidirectional, square rooted
%
A
100 % unidirectional, square rooted %
B
80 % unidirectional, square rooted
%
C
50 % unidirectional, square rooted
%
D
Free (100 % bidirectional)
pressure
E
Free (100 % bidirectional)
pressure
F
Free (100 % bidirectional)
pressure