9500/9600 Series Electric Strike

Installation Instructions

HES, Inc.

22630 N. 17th Ave.

Phoenix, AZ 85027

800-626-7590

www.hesinnovations.com

1

Diagram 1: Electrical Specifications

MINIMUM WIRE GAUGE REQUIREMENTS

SOLENOID VOLTAGE

12VDC

24VDC

200 feet or less

200 - 300 feet

300 - 400 feet

14 gauge

12 gauge

14 gauge

18 gauge

18 gauge

16 gauge

2

4

1

ASSA ABLOY, the global leader

in door opening solutions

Product Components

       
  #10-32 Final Lockdown Screw      
  12 & 24 Volt Pigtails   
    

1

2

      9500/9600 Electric Strike Body
      1/4”-20 x 1” Mounting Screws
       

3

4

ELECTRICAL RATINGS FOR SOLENOID

CONTINUOUS DUTY

12VDC

26.6

.45

24VDC

106.6

.225

Resistance in Ohms
Amps

Solenoid voltage is rated at +/- 10% indicated value.

3

Содержание 9500 Series

Страница 1: ...0 feet or less 200 300 feet 300 400 feet 14 gauge 12 gauge 14 gauge 18 gauge 18 gauge 16 gauge 2 4 1 ASSA ABLOY the global leader in door opening solutions Product Components 10 32 Final Lockdown Screw 12 24 Volt Pigtails 1 2 9500 9600 Electric Strike Body 1 4 20 x 1 Mounting Screws 3 4 ELECTRICAL RATINGS FOR SOLENOID CONTINUOUS DUTY 12VDC 26 6 45 24VDC 106 6 225 Resistance in Ohms Amps Solenoid v...

Страница 2: ...ransformers operate at higher levels than listed Any input voltage exceeding 10 of the solenoid rating may cause severe damage to the unit and will void the warranty Prepare Frame 4 Prepare the door jamb using the Installation Template located on page 4 with the exception of the 10 32 UNF threaded hole 5 Connect power wires and attach electric strike to jamb using the 1 4 x 20 cap screws provided ...

Страница 3: ... position as pictured away from the center of the strike in Figure 2 There are screws on both the left and right side of strike Both pairs of screws must be repositioned to convert the strike to Fail Safe Operation 3 Tighten both sets of 4 40 screws after they have been moved to the Fail Safe Operation position 4 For 9500 series strikes remove the Listed Fire Rated Hardware label if the strike is ...

Страница 4: ...4 8 4X 33 3 1 5 16 33 3 1 5 16 1 3 4 44 5 5 8 17 4 7 8 22 2 3 4 19 1 9 228 6 4 1 2 114 3 8 1 4 209 6 1 4 20 MOUNTING SCREWS SETSCREW LOCATION 1 Loosen the two 1 4 20 mounting screws 2 Adjust strike to appropriate horizontal position 3 Tighten the two 1 4 20 mounting screws 4 Lock down adjustment by tightening the setscrews 9500 9600 DIMENSIONS HORIZONTAL ADJUSTMENT Inches mm 3 4 190 CLEARANCE FOR ...

Отзывы: