between room-temperature and set-point exceed 1

, Auto MED-speed When exceed 2

, Auto HI-speed When exceed 3

 Control Damper (

H7

990

 

Y): The damper will be open when (1) room temperature is higher than set-point in cooling;(2)

room temperature is lower than set-point in heating, Otherwise the damper will be closed. 

 Control Motorized Valve under 2-pipe configuration (

H7

990 08

 DA/DB/DA2/DB2): If the difference between room

temperature and set-point exceed 1

, FCU valve will be open; if room temperature and set-point are equal, 

H7

990 08 

 

DA/DA2

will close the FCU valve with the fan still running, 

H7

990 08

 

DB/DB2 will close the FCU valve and Fan both.

 Control FCU Valve under 4-pipe configuration (H

7

990 08

 

FCV2): In cooling, when the room temperature is higher than

 

set-point,  the  cooling  Valve  will  be  opened.  Otherwise  it  will  be  closed.  Heating  valve  is  always  closed.  In  heating,  When  the 

room temperature is lower than set-point, the heating valve will be opened. Otherwise it will be closed. Cooling valve is always 

closed. 

DEFROST (LOW TEMPERATURE PROTECTION) 

  Description:  when  the  thermostat  turns  off  and  the  room  temperature  is  lower  than  5

˚

c,  it  will  be  turned  on 

automatically in heating mode with 

 

” showing, under 

H

7990 08

 

DA/DB/DA2/DB2/FCV2 models, the system will be in heat

mode and fan runs in high speed. 

Under 

H7

990 08

 Y model, the motorized damper will be open. The thermostat will turn off

 

when room temperature is higher than 7

˚

 Set low temperature protection: Turn off the thermostat, press 

“ ” and “

” buttons simultaneously and hold for 3 

seco

nds, it will display “00” or “01”, press “

” or “

” key to adjust. “00” indicates low temperature protection invalid, “01” 

indicates low temperature protection function valid. The default is 

“00”. 

WIRING DIAGRAMS 

MOUNTING 

1. Open  the  main  control 
panel:  put  the  screwdriver 
(3.5mm)  into  the  block 
4mm  along  the  bevel. 
Prize up, open the clips.

2. Take off the wires.

3. As  per  wiring  diagram,
connect  it  with  terminals, 
fixed by the screwdriver.

4.

Put  the  connected 

thermostat  onto  the  back 
panel in the wall, then fix it 
with  the  two  screws  in  the 
packing box.

5. Put  the  cover  with  30 
degree  angle,  then  fix  the 
up two clips.   

6. Push  the  places  of  the 

two  down  clips,  fix  the 
cover, 

and 

finish 

the 

installation. 

H7

990

 

08 

DA/DB

Val 

Med 

Low 

Fan 

Valve 

AC85

260V    50/60Hz 

N    L 

Hi 

H7

990 

08Y

Damper 

VC 

VO 

AC85

260V    50/60Hz 

N    L 

H7

990

 

08 

DA2/DB2

 

VO 

Med 

Low 

Fan 

Valve 

VC 

AC85

260V    50/60Hz 

N    L 

Hi 

H7

990

 

08 

FCV2

Cooling 

Med 

Low 

Fan 

Val 1 

Val 2 

Heating 

AC85

260V    50/60Hz 

N    L 

Hi 

HERZ Armaturen Gws.m.b.H

Richard-Strauss-Strasse 22,1230 Vienna, Austria.

2