13A. In both cases, the switch must be double pole (disconnecting both live and neutral conductors) and form 
part of the fixed wiring in the installation in accordance with applicable wiring regulations. The spur fuse should 
also be rated in accordance with the appropriate table. In either case the switch used to operate the Herschel 
IR360 must be readily accessible. 
 
The cable used to connect to the existing wiring should be correctly rated solid core wiring cable. Please note 
that  the  use  of  flexible  appliance  cable  with  stranded  conductors  for  permanent  wiring  (except  for  the  final 
connection between a cable outlet and the fixed equipment) is prohibited by IEE wiring regulations. 
 
Where applicable, these regulations preclude the use of a 13A plug and socket for powering the Herschel IR360. 
For the final connection to the Herschel  IR360, only the flexible cable and cable entry supplied with the unit 
must be used. The cable must connect to the supply in a suitable enclosure or cable outlet designed for that 
purpose. The cable outlet current carrying capacity must be greater than the recommended fuse current rating 
given in Table 1. 
 
If the flexible cable is taken through a wall for connection purposes, suitable conduit or mechanical protection 
must be used through the wall to protect the cable from mechanical damage within the wall. The mounting 
position  of  the  unit  must  ensure  that  any  mechanical  damage  to  the  flexible  cable  is  unlikely.    Any  exposed 
flexible  cable  is  to  hang  down  (not  tied  UP)  and  must  have  adequate  clearance  from  the  heater  to  prevent 
scorching or damaging the cable.  
 

Colour coding used in the supplied mains cable:  BROWN wire is to be connected to LIVE (‘L’),

 the BLUE wire to 

NEUTRAL (‘N’) and the GREEN/YELLOW wire to EARTH (‘E’). 

 

 

MOUNTING POSITION: 

The Herschel IR360 must be located in a position to allow 
proper and efficient use but one that ensures hot parts are 
not  touched  accidentally.  The  recommended  installation 

height of the IR360 is 2.3m to 2.5m (90”

-

98”) from the floor 

and under no circumstances is it to be installed at less than 
2.3m from the floor.  In all cases it should be installed at a 
height  where  it  cannot  be  touched  in  operation.  
Consideration  should  be  given  to  any  temporary  or 
occasional additions such as stages or platforms, and  the 
height should be adjusted accordingly.  
 
The  Herschel  IR360  should  be  firmly  and  permanently 
attached  to  the  ceiling.    A  ceiling  mounting  plate  is  not 
supplied with this heater. A suitable mounting plate must 
be fitted having adequate strength to bear a load of 16kg 
(equal to 4 times the mass of the unit).   
 
The  Herschel  IR360  should  be  installed  with  a  minimum 
clearance of 300mm (11.8

”) between the top surface of the 

heater and the ceiling.  
 

 