Page 4
For technical questions, please call 1-888-866-5797.
Item 56845
GROUNDING INSTRUCTIONS
TO PREVENT ELECTRIC SHOCK AND
DEATH FROM INCORRECT
GROUNDING WIRE CONNECTION:
Check with a qualified electrician if you are in doubt
as to whether the outlet is properly grounded.
Do not modify the power cord plug provided with
the tool. Never remove the grounding prong from
the plug. Do not use the tool if the power cord or
plug is damaged. If damaged, have it repaired by a
service facility before use. If the plug will not fit the
outlet, have a proper outlet installed by a
qualified electrician.
Double Insulated Tools: Tools with
Two Prong Plugs
1. Tools marked “Double Insulated” do not
require grounding. They have a special
double insulation system which satisfies
OSHA requirements and complies with
the applicable standards of Underwriters
Laboratories, Inc., the Canadian Standard
Association, and the National Electrical Code.
2. Double insulated tools may be used in either of the
120 volt outlets shown in the following illustration.
(See Outlets for 2-Prong Plug.)
Outlets for 2-Prong Plug
Extension Cords
1.
Grounded
tools require a three wire extension cord.
Double Insulated
tools can use either
a two or three wire extension cord.
2. As the distance from the supply outlet increases,
you must use a heavier gauge extension cord.
Using extension cords with inadequately sized wire
causes a serious drop in voltage, resulting in loss of
power and possible tool damage.
(See Table A.)
3. The smaller the gauge number of the wire, the
greater the capacity of the cord. For example,
a 14 gauge cord can carry a higher current
than a 16 gauge cord.
(See Table A.)
4. When using more than one extension cord to make
up the total length, make sure each cord contains at
least the minimum wire size required.
(See Table A.)
5. If you are using one extension cord for more
than one tool, add the nameplate
amperes
and use the sum to determine the required
minimum cord size.
(See Table A.)
6. If you are using an extension cord outdoors, make
sure it is marked with the suffix “W-A” (“W” in
Canada) to indicate it is acceptable for outdoor use.
7. Make sure the extension cord is properly wired
and in good electrical condition. Always replace
a damaged extension cord or have it repaired
by a qualified electrician before using it.
8. Protect the extension cords from sharp objects,
excessive heat, and damp or wet areas.
TAbLE A: RECOMMENDED MINIMUM WIRE
GAUGE FOR EXTENSION CORDS* (120/240 VOLT)
NAMEPLATE
AMPERES
(at full load)
EXTENSION CORD
LENGTH
25´
50´
75´ 100´ 150´
0 – 2.0
18
18
18
18
16
2.1 – 3.4
18
18
18
16
14
3.5 – 5.0
18
18
16
14
12
5.1 – 7.0
18
16
14
12
12
7.1 – 12.0
18
14
12
10
-
12.1 – 16.0
14
12
10
-
-
16.1 – 20.0
12
10
-
-
-
* based on limiting the line voltage drop to five volts at
150% of the rated amperes.