HELVAR SF-PIR-SW-01 Скачать руководство пользователя страница 4

4

Helvar Ltd 

Hawley Mill 

Hawley Road 

DARTFORD 

DA2 7SY 

UNITED KINGDOM 

www.helvar.com

Doc. 7860341, issue 2, 2015-12-15

Helvar

 | Data is subject to change without notice.

Conformity and standards

EMC emission:

EN60669-2-1:2004 inc 

A12:2010

EMC immunity:

EN60669-2-1:2004 inc 

A12:2010

Safety:

EN60669-2-1:2004 inc 

A12:2010

Environment:

Complies with WEEE and RoHS 

directives.

Version information

Hardware version:

Rev. 1

Hole diameter: 

Ø 

75 mm

2

60

77

85

Dimensions (mm)

Technical Data

Electrical data

External power: 

Terminal block 

Wire section: 0.5 mm² – 

2.5 mm² solid or stranded

Cable rating:

All cables must be mains 

rated.

Mains supply:

230 VAC, 50 Hz

Loads:

6 A resistive (e.g. heater) 

4 A incandescent 

3 A fluorescent ballast / LED 

driver 

1 A inductive (e.g. fan/motor) 

Mains LED lamps: Equivalent 

to 1000 W halogen load 

Min. load: 2 W resistive, 

suitable for most energy saving 

lamps, LEDs and emergency 

fittings.

External 

protection:

6 A maximum (MCB or fuse)

Illuminance:

10 lx to 1000 lx and maximum 

(photocell inactive) at the PIR 

switch.

Sensors

Presence detector:

PIR (Passive InfraRed)

Detection range:

360° with up to 7 m diameter 

when mounted at a 2.8 m 

ceiling height

Time:

10 s to 40 min

Mechanical data

Mounting hole 

diameter:

75 mm

Bezel diameter:

85 mm

Recommended 

clearance depth 

(incl. 50 mm for 

cabling):

80 mm (without protective 

cover) 

100 mm (with protective cover)

Material (casing):

Flame-retardant polycarbonate

Finish / Colour:

Matt / White RAL9003

Weight:

100 g

IP code:

IP20

Operating conditions

Ambient 

temperature:

+10 °C to +35 °C 

Note: The temperature 

difference between the detection 

target and the background must 

be at least 4 °C.

Relative humidity:

Max. 90 %, noncondensing

Storage 

temperature:

–10 °C to +70 °C