2.8 m

7 m

Installation Notes

•  Position the sensor so that the occupants of the room are normally inside the detection zone.
•  Do not fix the sensor to an unstable or vibrating surface.
•  Do not install the sensor within 1 m of any lighting, forced air heating, or ventilation equipment.
•  Do not install several sensors in parallel near lamps that emit infrared radiation if these lamps are switched via another 

PIR switch. This can cause false triggering.

•  Make sure that the wires and cables are securely held within the connection terminals.
•  Do not connect on a circuit with large inductive loads, as induced spikes can cause false triggering or damage the sensor.
•  Protect the sensor by a 6 A MCB or fuse.
•  Disconnect the sensor from the circuit before performing insulation testing of the wiring circuit.

L: Live in 

SW¹: Switch input (only in absence mode) 

N: Neutral in 

SL: Switched live

Single sensor

Multiple sensors

L

L

L

N

SW

1

SL 

N

L

N

SL

SL

SL

Mains-rated 

retractive wall switch 

~230 VAC 

Only available 

in absence mode.

(Presence detection mode only)

Area 

of lower 

sensitivity

Area 

of higher 

sensitivity

Connections

www.helvar.com   

Detection Pattern