8
µDim
Doc No:
T13 144 1C
2. T
echnical Data
Data is subject to change without notice. More information at: www.helvar.com
5m
12m
8m
2.8m
Recommended mounting location
Detection area
Sensor head
• Avoid direct sunlight entering the sensor
• Do not site within 1m of forced air heating or ventilation.
• Do not fix to a vibrating surface.
• Avoid metallic objects directly in front of the sensor head.
• Do not fit to a suspended luminaire
• When installing the sensor head behind a glass /
polycarbonate diffuser will reduce the detection range by
approximately 20%.
Note:
On maximum sensitivity, the detector unit is extremely sensitive
to movement and may detect through glass, thin walls or partitions.
If this causes a problem, reduce its sensitivity using the SA-IR-PROG
Programmer.
Lens
Green LED - time
Red LED - lux / presence setting indicator
Yellow LED - sensitivity / absence setting indicator
SL-MW-DA µDim Microwave DALI Sensor
Technical specifications
• Supply voltage
220 - 240 V AC, 50 Hz
• Max load capacity
Relay Output - 2 A
Dimmed Output - 4 x DALI ballasts
• Light level
Light to dark
• Connections
Integral RJ11 cable between
supply unit and sensor head
• Terminals (supply unit)
1.5mm
2
(solid core cable only)
Material
• Sensor head, surface mount baseplate ,
flush bracket — Flame retardant ABS
• Flange mount bracket & Lens—PMMA (Clear acrylic)
• Power supply unit housing — Flame retardant polycarbonate
• Type
Class 2
• Operating Temperature -10°C to 50°C
SAFETY
The microwave radiation emitted by these units is extremely
low power. At a distance of > 50mm the power density is <6%
of the ANSI IEEE C95.1 –1991 recommended microwave
power density. At a distance of 5mm from the unit it is <84% of
recommended power density.
Conformity
EMC-89/336/EEC
LVD-73/23/EEC