![Helmholz 700-158-3DP02 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/helmholz/700-158-3dp02/700-158-3dp02_quick-start-manual_2122244003.webp)
Quick Start Guide DP/PN Coupler
3
2. Introduction
This document explains the initial commissioning of the DP/PN Coupler
(700-158-3DP02, V2)
.
Further information can be found in the manual. You can find this at
or scan the QR code directly.
3. Function of the DP/PN Coupler
With the DP/PN Coupler, a simple and uncomplicated connection of PROFIBUS
to PROFINET networks is possible. The DP/PN Coupler allows data transmission
between the PROFIBUS master and the PROFINET controller and is planned both on
the PROFIBUS and PROFINET sides as a slave (device).
Received input data on one of the network sides is made available as output data to
the other network side. The IO data transfer takes place live and as quickly as possible
without additional handling blocks.
The maximum size of the transmitted data is 244 bytes of input data and 244 bytes of
output data (max. IO size of PROFIBUS-DP). Up to 16 slots for IO modules of 1 byte
and up to 64 words are available.
The incorporation into the PLC engineering tool is made possible by a GSD or GSDML
file, special configuration software isn’t necessary.