Helmholz 700-158-3DP02 Скачать руководство пользователя страница 10

Quick Start Guide DP/PN Coupler

10

7.2 Assign a PROFINET device name to the DP/PN Coupler

When the configuration of the DP/PN Coupler has been completed in the hardware 

configurator of the engineering tool, it can be loaded into the PLC.

In order that the DP/PN Coupler can be found by the PROFINET controller, the  

PROFINET device name must be assigned to the DP/PN Coupler. To this purpose, 

 

use the function “Assign device name”, which you can access in the Offline menu 

with the right mouse button when the DP/PN Coupler is activated.

With the “Update list” button, the network can be browsed for PROFINET partici-

pants. The PROFINET device name can be assigned to the device with “Assign name”.
The clear identification of the DP/PN Coupler is ensured here by the MAC address of 

the device. The MAC address of the device can be found on the device front of the 

DP/PN coupler.

The Helmholz IPSet tool, which can be downloaded at no charge from the Hemholz 

website, can also be used to set the PROFINET name.
If the DP/PN Coupler has been assigned the correct name, it is recognized by the  

PLC and configured. If configuration has taken place correctly, the PROFINET “BF” 

LED should be off.

If configuration has also taken place correctly on the PROFIBUS side, the PROFIBUS 

“BF” LED should also be off. When both network sides have been configured appro

-

priately (number and size of the IO areas agree), the “SF” LEDs on both sides should 

also be out on both sides and data transmission be underway.

DP/PN Coupler 

IPSet

SCAN  

QR CODE 

 

TO GET 

FIRMWARE

Содержание 700-158-3DP02

Страница 1: ...Quick Start Guide DP PN Coupler V2 Version en as of FW 2 00 6 www helmholz com...

Страница 2: ...fulfills all safety requirements including all applicable laws regulations provisions and standards Intended use The device has a protection rating of IP 20 open type and must be installed in an elect...

Страница 3: ...ontroller and is planned both on the PROFIBUS and PROFINET sides as a slave device Received input data on one of the network sides is made available as output data to the other network side The IO dat...

Страница 4: ...MAC address of the PROFINET connection Note The housing has no connection to earth Please connect the funcitional earth Terminal FE correctly with the reference potential 4 Connection The RJ45 X1 P1 a...

Страница 5: ...US address The PROFIBUS address of the DP PN Coupler can be set using the DIP switch of the device see sketch The DIP switch is a toggle switch If the upper toggle is pressed the respective positi on...

Страница 6: ...th the DP PN Coupler Now insert the desired IO modules into the plug points IO modules for 1 2 4 8 16 32 64 Bytes and 64 words are available for input and output Consistent modules are also available...

Страница 7: ...PLC if the power supply fails at PS1 left side or PS2 right side Data validity display DIA The validity of the data is displayed in the least significant bit bit 0 of the first input byte 0 Data could...

Страница 8: ...nnect the PROFINET network of the PROFINET CPU with the DP PN Coupler Now insert the desired IO modules into the plug points IO modules for 1 2 4 8 16 32 64 and 128 bytes are available for input and o...

Страница 9: ...to PS1 left side or PS2 right side Data validity display DIA The validity of the data is displayed in the bit with the lowest value Bit 0 of the first input byte of the corresponding PROFINET side 0...

Страница 10: ...e device with Assign name The clear identification of the DP PN Coupler is ensured here by the MAC address of the device The MAC address of the device can be found on the device front of the DP PN cou...

Страница 11: ...ew of the status and the configuration of the device as well as the possibility to perform a firmware update Please download the current firmware from www helmholz com or scan the QR code Note Calling...

Страница 12: ...red The device is configured On The device has no configuration the PROFIBUS address is incor rect or there is no connection with the PROFIBUS master The device has no configuration the PROFINET devic...

Страница 13: ...essing topology detection LLDP DCP diagnosis alarm conformance class B PROFIBUS interface Transmission rate max 12 Mbps autom detection Protocol PROFIBUS DP I O image size max 244 bytes of input 244 b...

Страница 14: ...Quick Start Guide DP PN Coupler 14...

Страница 15: ...Quick Start Guide DP PN Coupler 15...

Страница 16: ...on the Internet at www helmholz de Our products contain open source software among others This software is subject to the respectively relevant license conditions We can send you the corresponding li...

Отзывы: