6

 

● Identification in accordance with Directive at least 

II (2) G.

The motor protection switch must be wired in 

accordance with wiring diagram Fig. D. The motor 

protection switch should be set to the nominal motor 

current (not 

I

max

).

Prescribed setting/tripping values for motor protecti-

on switch, see rating plate.

The switch must trip in the event of a short-circuit.

Once all causes of faults have been eliminated, the 

connected motor must not start up again automati-

cally. It may only be switched on again manually 

(switch-on inhibit).

7 Duties of the installer and the operating 

company

The fan may only be operated at permissible ambi-

ent and airstream temperatures of -20 to +50 °C and 

only if fully mounted.

The fan should be regularly checked and maintained 

by an electrician trained in explosion protection  

 Chapter 19.

Cleaning and maintenance intervals should be 

determined by the operating company in accor-

dance with EN 60079-17 – frequency depends on 

ambient conditions and anticipated limitations. 

Shorten the maintenance intervals in the event 

of dust or a corrosive atmosphere. 

Additional 

safety requirements should be 

observed

 during mounting and operation, e.g. in 

accordance with

 

EU Directive 1999/92/EC, ATEX 137: implemen-

ted in Germany with the Ordinance on Industrial 

Safety and Health.

 

EN 60079-14: Design, selection and erection of 

electrical installations.

 

the national accident prevention requirements.

8  Safety instructions for users

 

!

DANGER

Explosion hazard due to spark formation if 

foreign bodies are inserted into the unit. 

Do not 

insert any objects in the unit.

 

!

CAUTION

Danger of injury due to rotating impeller and 

suction. Hair, clothing, jewellery etc. may be 

pulled into the fan if you get too close to it. 

During operation always keep far enough away to 

prevent this from happening.

 

!

CAUTION

Risks for people (including children) with 

reduced physical, sensory or mental capabili-

ties or a lack of knowledge. 

The fan may not be 

used or cleaned by children or people with reduced 

capabilities.

 

!

CAUTION

Hot motor surfaces may result in skin burns if 

touched. 

Do not touch hot motor surfaces. Always 

wait until the motor has cooled down.

Switching unit on / off

The fan is switched on or off with an optional switch.

The fan is designed for continuous operation (S1). 

Frequently switching on/off may result in improper 

heating and should be avoided.

10  Reversing mode

Fan not suitable for reversing mode.

11 

Action to take in the event of a fault

Check whether the motor protection switch has 

responded. Unplug the fan from the mains in the 

event of operational disturbances. Before switching 

on again, have trained specialists perform trou-

bleshooting and remedy faults found. This applies 

in particular after the motor protection switch has 

tripped. If faults reoccur, send the unit to our factory 

for repairs.

Mounting of unit by electrician  

trained in explosion protection 

12  Safety instructions

Under no circumstances use the unit for purpos

-

es other than those for which it was intended 

 

Chapter 5.

 

!

DANGER

!

 

Danger from electric shock. 

Whenever work-

ing on the fan, release the supply current circuits, 

secure to prevent them from switching on again 

and ensure the unit is de-energised. Attach warning 

sign in clearly visible place. Ensure that there is no 

explosive atmosphere.

!

 

Explosion hazard. Degree of protection is 

not ensured if the cables are incorrectly insert-

ed into the terminal box.

Ensure degree of protection by correctly inserting 

the cables into the terminal box.

!

 

Explosion hazard when operating with unit 

not fully mounted and if air inlet/outlet is not 

correctly protected.

The fan may only be operated if the unit is fully 

mounted and with the protective devices  

(EN 60529)

 for the air channel fitted. Ensure that 

foreign bodies cannot be sucked into the unit and 

ducts.

!

 

Explosion hazard/danger of injury from an 

incorrectly mounted fan or a falling fan. 

Only mount on walls/ceilings with sufficient 

load-bearing capacity and sufficiently dimensioned 

mounting material. Mounting material is to be 

supplied by the customer. During installation, do 

not allow people to stand under the installation 

location.

!

 

Explosion hazard due to incorrect adjust-

ment.

The rotating fan parts were adjusted in the man-

ufacturer's factory. The unit must not therefore be 

taken apart. The temporary removal of the terminal 

box cover during unit installation is the only excep-

tion to this restriction.

 

NOTICE

: Damage to the unit

Loss of IP degree of protection if fan is mount-

ed in damp rooms with air being transported 

upwards. 

Do not mount the fan in damp rooms 

with air being transported upwards.

13  Transport, storage

 

!

DANGER

Danger from unit falling if transporting with 

unauthorised transport equipment.

 

Use lifting and transport equipment suitable and 

approved for the fan and transport weight.

Do not stand under a suspended load.
Note weight and centre of gravity (centre).

  

Observe the maximum permitted loading capacity 

for lifting gear and means of transport. For total 

weight 

 rating plate on fan.

During transport 

do not place load on sensitive 

components

, such as impeller or terminal box.  

Fit transport equipment correctly.

 

!

CAUTION

Risk of cuts from metal housing plates 

with sharp edges. 

Wear personal protec-

tive equipment (cut-resistant gloves) for 

installation.

 

Only ship unit in original packaging.

 

Store unit in dry location (-25 to +55 °C).

14  Technical data 

 Rating plate on unit.

Nominal size, depending 

on type

180, 200 or 250

Degree of protection of 

motor

IP54

Air volume

 Rating plate

Sound power level

 Fig. A/rating plate:

Vibration values  

(ISO 14694)

BV-3

Weight

 Rating plate

15  Ambient/operating conditions

 

Permitted ambient and airstream temperature: 

-20 °C < Ta < +50 °C. For special versions  

 rating plate.

 

Division of maximum surface temperature into 

classes. Temperature class T... 

 rating plate.

Temperature class

T1 T2 T3 T4 T5 T6

Maximum surface 

temperature [°C]

450 300 200 135 100 85

16  Mounting

During mounting, note the applicable installation 

requirements 

 especially EU Directive 1999/92/EC, 

EN 60079-14 and VDE 0100 (in Germany).

Mounting instructions

 

NOTICE

: Damage to the unit

Units with pre-installed line feedthrough to the 

terminal box may be damaged if the connec-

tion line is pulled or the unit is lifted using the 

line. 

Do not pull connection lines or lift the unit 

using the lines.

RRK .. Ex - fan:

 

for permanent installation in ducts with ventila-

tion duct or flexible duct suited to the unit type 

(nominal size).

 

for surface mounting on

 duct, wall, foot

 with 

sufficient load-bearing capacity.

 

Any installation position, do not install in 

damp rooms with air being transported 

upwards.

 

for ventilation or air extraction, depending on the 

installation position.

 

Unit connection sockets on both sides for direct 

installation in ventilation ducts.

UK

Содержание RRK 180 Ex

Страница 1: ...atoren MONTAGE UND BETRIEBSVORSCHRIFT NR 90 527 Helios Ventilatoren MONTAGE UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D UTILISATION Radial Rohrventilatoren Ve...

Страница 2: ......

Страница 3: ...0 178 142 120 92 275 RRK 200 Ex 278 177 195 198 179 140 115 299 RRK 250 Ex 304 205 210 248 180 160 128 311 Schallleistungspegel Sound power level Niveau de puissance acoustique LWA7 dB A RRK 180 Ex 66...

Страница 4: ...fahr durch Funkenbildung Einen freien Luftein austritt unbedingt mit einer Schutzvorrichtung nach EN 60529 versehen z B mit Schutzgitter Ein beidseitiger Eingreifschutz Schutzgitter nach EN 13857 ist...

Страница 5: ...A Typenschild Schwingungswerte ISO 14694 BV 3 Gewicht Typenschild 15 Umgebungs Betriebsbedingungen Zul ssige Umgebungs und F rdermitteltem peratur 20 C Ta 50 C F r Sonderaus f hrungen Typenschild Ein...

Страница 6: ...hlerschleifen Impedanz TN System oder Erdungswiderstand IT System zufriedenstellend IX Automatische elektrische Schutzein richtungen richtig eingestellt automa tische R ckstellung nicht m glich X Spez...

Страница 7: ...ation and electrical connections in accordance with the wiring diagrams provided in these instruc tions In addition you must be able to recognise assess and avoid ignition and explosion hazards and ri...

Страница 8: ...atmosphere Explosion hazard Degree of protection is not ensured if the cables are incorrectly insert ed into the terminal box Ensure degree of protection by correctly inserting the cables into the ter...

Страница 9: ...th a contact opening of at least 3 mm per pole with permitted voltage and frequency rating plate with explosion protection terminal box provided with protective conductor terminal at mains end in term...

Страница 10: ...ce Remove dirt and foreign particles Repairs If unit components are worn send fan to our factory Unit component replacements and or repairs are only permitted in the manufacturer s factory 20 Fault re...

Страница 11: ...tie d air l air libre notamment si le ventila teur est accessible aux personnes Exploitation uniquement autoris e avec protection bilat rale contre l atteinte des zones dange reuses Les zones permetta...

Страница 12: ...de montage ATTENTION Endommagement de l appareil Les appareils munis d une arriv e pr install e vers le bornier risquent d tre endommag s si on tire sur la gaine de raccordement ou si l ap pareil est...

Страница 13: ...e visible constat sur les c bles et conduites IV Les branchements lectriques sont fix s V Les bornes de raccordement sont serr es correctement VI La r sistance d isolation IR des bobines de moteur est...

Страница 14: ...missibles la r gularit de fonctionnement des roulements La long vit des roulements est de 40000 heures en fonction de l application le vissage correct des conduites dans le bornier un endommagement ve...

Страница 15: ...13...

Страница 16: ...8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensstra e 15 6023 Innsbruck Colchester Essex CO4 9HZ www h...

Отзывы: