3.5
Connection of the voltage supply
1. A plastic-sheathed cable and /or in a moist room a NYM cable is to be used.
2. Cable exit from the wall at least 180 mm (Fig.3)
3. Puncture cable grommet with a round tool or directly with the supply cable (Fig.5, Pos. 3).
4. Remove cable jacket at least 100 mm in length. Strip insulation 7mm in length (Fig.6).
5. Push cable carefully through cable grommet.
6. If with installed supply cable, the cable grommet does not enclose the plastic-sheathed cable evenly, the grommet
must be sealed additionally e.g. with silicone (Fig.6).
Otherwise the IP protection expires.
7. Run cable in conduit and connect according to wiring diagram (page 9).
5
MiniVent M1/100 P/120 P
Installation and Operation Instructions
fig.6
fig.7
1. Press cover of control board
➋
on casing and
fasten with screws.
2. Snap in facia.
➊
➊
➋
➌
- Length of single conductor 100 mm
- Length of stripped insulation 7 mm
- Strip plastic-sheathed cable flush with conduit.
100 mm
fig.8
Mount guide
vane with
back draught
shutter at the
end of the
duct or just
omit it.
Duct channel
90° bend
Assembly at cramped
place conditions
Snap in facia
7 mm
UK
ATTENTION
☞
Abb.9
Standard installation
WES 1.. or
TWH 1..
Guide vane with
back draught
shutter
Fan
Room area
outside
core drill hole
M1/100 =
Ø 115 mm
M1/120 =
Ø 130 mm