37
Observe the saved information regarding the most recent
discharge test shown here, with fields for days since the
Last
Battery Discharge Test
,
Status
(Pass or Fail),
Discharge
Time
,
End Voltage
at the completion of the test, and the
Amp Hours Discharged
during the test. The scheduled date
and time until the next automatically repeating test will also
be shown if this feature has been enabled.
5.3. Alarms
Select the Alarms page (
STATUS
tab) to view the status of currently
active alarms as well as the alarm history.
Click on the
SETTINGS & CONTROL
tab to configure the actions to
be taken when power alarms are triggered. To save any changes to
the alarm settings, click on Save Settings
at the bottom of this page.
The e-mail settings on the
Network Setup
page must be configured
correctly before any e-mail notifications can be sent.
DC OUTPUT FAILURE ALARM
The alarm latches the output off, and clears when the DC output is
manually re-enabled.
•
Activate Alarm Form C Contact:
If this box is checked, the
alarm form “C” contacts on the power supply will indicate a
fault condition when the Output Voltage or current rises
above approximately 110% of the max-rated output.
•
Send E-mail:
If this box is checked, an e-mail alarm
notification will be sent when a DC output failure occurs.
AC INPUT FAILURE/SYSTEM FAILURE ALARM
The alarm latches the output off when the AC voltage fails, and
automatically clears when the AC input voltage rises above
approximately 100Vac for 3 seconds, and any internal fault is
resolved.
•
Activate Alarm Form C Contact:
If this box is checked, the
alarm form “C” contacts on the power supply will indicate a
fault condition when the AC input voltage falls below
approximately 90Vac, or there is an internal power supply