32
Auto-Restart Delay:
Set delay time (5 to 240s) that output will
remain off when output is remotely disabled using the Auto-Restart
button. The unit will then automatically restart after the Restart Delay
period.
5.2. Battery Backup
Select the Battery Backup page (
STATUS
tab) on units with the
optional Battery/LVD port (SBC suffix units) to observe the status of
the external battery. You may check battery voltage, battery current
(+ is charging, - is discharging), temperature (if ICT-TMP probe
installed), Net Ah count (approximate Ah discharged from the battery,
where 0Ah denotes full charge), the estimated run time remaining at
the current load when in back-up mode, approximate battery state of
charge in %, and the status of the LVD (connected, or disconnected).
Click on the
Settings & Control
tab to set all battery related
parameters on units with the optional Battery/LVD port (SBC suffix
units). Click the Save Settings button after making changes to this
page.
Output Voltage Control:
automatically adjust the output voltage of
the power supply according to the battery temperature, when the
optional temperature probe (ICT-TMP) is installed.
•
Temperature Coefficient/cell:
set the desired temperature
change in -mV/°C per cell, according to the battery
manufacturer’s recommendations. The default setting of 0mV
disables the compensation. (A typical lead-acid
compensation value is -4mV/°C/cell, which is -24mV/°C for a
12V battery)
Battery Charge Current Limit:
Limit the maximum battery charge
current provided through the optional Battery LVD port, while still
allowing the full rated current to be drawn from the main output.
•
Charge Current Limit:
Set the maximum charge current (A)
as recommended by the battery manufacturer. Default is the
maximum current rating for the unit.
Содержание ICT Platinum Series
Страница 2: ...www heliosps com 2 Rev 1 0 Nov 2019...