Auto-Restart Delay: 

Set delay time (5 to 240s) that output will 

remain off when output is remotely disabled using the Auto-Restart 
button. The unit will then automatically restart after the Restart Delay 
period. 
 
 
 

5.2.  Battery Backup 

 
Select the Battery Backup page (

STATUS

 tab) on units with the 

optional Battery/LVD port (SBC suffix units) to observe the status of 
the external battery. You may check battery voltage, battery current 
(+ is charging, - is discharging), temperature (if ICT-TMP probe 
installed), Net Ah count (approximate Ah discharged from the battery, 
where 0Ah denotes full charge), the estimated run time remaining at 
the current load when in back-up mode, approximate battery state of 
charge in %, and the status of the LVD (connected, or disconnected). 
 
Click on the 

Settings & Control

 tab to set all battery related 

parameters on units with the optional Battery/LVD port (SBC suffix 
units). Click the Save Settings button after making changes to this 
page. 
 

Output Voltage Control:

 automatically adjust the output voltage of 

the power supply according to the battery temperature, when the 
optional temperature probe (ICT-TMP) is installed. 
 

 

Temperature Coefficient/cell:

 set the desired temperature 

change in -mV/°C per cell, according to the battery 
manufacturer’s recommendations. The default setting of 0mV 
disables the compensation. (A typical lead-acid 
compensation value is -4mV/°C/cell, which is -24mV/°C for a 
12V battery) 

 

Battery Charge Current Limit: 

Limit the maximum battery charge 

current provided through the optional Battery LVD port, while still 
allowing the full rated current to be drawn from the main output. 
 

 

Charge Current Limit:

 Set the maximum charge current (A) 

as recommended by the battery manufacturer. Default is the 
maximum current rating for the unit. 

 
 
 
 

Содержание ICT Platinum Series

Страница 1: ...Instruction Manual 855 339 001 Australia sales heliosps com au Middle East Asia sales heliosps asia New Zealand sales heliosps co nz Your DC Power Solutions Partner...

Страница 2: ...www heliosps com 2 Rev 1 0 Nov 2019...

Страница 3: ...LEL OPERATION 23 4 1 SHARE Interface Connector 24 4 2 Configuring the Power Supplies for Parallel Operation 24 4 3 Connecting the Power Supplies in Parallel 25 4 4 Advanced Parallel Operation with TCP...

Страница 4: ...rating for short circuit protection Ensure dc polarities and rated voltages are correct for both the load and battery connections to the unit Ensure all connections are properly tightened before power...

Страница 5: ...Output voltage can be easily and accurately adjusted over standard battery operating voltage ranges using the Intelligent Power Control interface on the front panel Standard Ethernet port included for...

Страница 6: ...input connector plug 3pin and 7 pin REMOTE connector plug DC output bus bar cover and mounting hardware installed Two Three with B option Bus bar bolts with locking nuts for output wiring Two rack mou...

Страница 7: ...maximum battery charge current from the optional BAT port can be set independently from the main output current limit WARNING Potential for personal injury or damage to property and equipment due to...

Страница 8: ...ht and secure using four standard rack nuts and bolts not provided After the unit is mounted connect the load battery and supply wiring as outlined in the steps below Refer to the back panel illustrat...

Страница 9: ...n and disconnect device Otherwise damage to the unit load battery and personal injury may occur if the battery is inadvertently connected in reverse polarity or the output circuit is over loaded or sh...

Страница 10: ...B LVD equipped models to pin 4 and 5 to automatically compensate the charging voltage according to the battery temperature Apply the probe body to the side of the middle battery case using the provid...

Страница 11: ...e front of the Platinum Series power supply allows you to view the status of the unit and modify the power supply settings The Control Panel consists of the following Figure 2 Front Panel Display and...

Страница 12: ...Use the Up Down keys on the Control Panel to scroll to the System Status screen and then press the Enter key The System Settings screen will appear 2 Using the Up Down keys scroll to the Output Voltag...

Страница 13: ...wn keys change the DC output setting to On and then press the Enter key The DC output will now be enabled with the output voltage and current limit set as entered above 8 Press the Back key to return...

Страница 14: ...link when the power supply is in current limit SYSTEM SETTINGS SCREEN From the System Status screen press Enter to move to the System Settings screen The System Settings screen allows you to modify th...

Страница 15: ...talled These settings allow you to adjust the battery Low Voltage Disconnect LVD points configure the battery maximum charge current float voltage temperature compensation Equalize charge settings and...

Страница 16: ...ttery Capacity Rating Ah Battery Discharge Rate Set the Battery discharge rate hrs used for capacity spec typically either 10 or 20hrs Low SOC Alarm Set the Low Battery State of Charge Alarm If the Ba...

Страница 17: ...eature on any type of sealed battery Ensure the battery compartment is well ventilated to avoid any risk of explosion Do not exceed the Equalize voltage setting recommended by the battery manufacturer...

Страница 18: ...Time limit as the battery was not able to power the load for the desired duration NOTE This test must only be done when AC power will be present during the test and for adequate time after the test t...

Страница 19: ...the parallel settings PARALLEL SETTINGS SCREEN From the Parallel Status screen press Enter to move to the Parallel Settings Screen See the Smart Parallel Operation section for more information on conf...

Страница 20: ...m date and time are normally set by the network These may be manually set see Network GUI Operation Communication Basic Setup section NETWORK STATUS SCREEN View the Network Status Screen to check the...

Страница 21: ...see the Control Panel Menu Password Reset section for instructions on how to clear the password Set LCD Password Allows you to set the Control Panel menu password Clear LCD Password Allows you to cle...

Страница 22: ...em Status screen is displayed on the Control Panel display 3 Release the Back and Enter keys You will no longer be prompted for a password on any of the Control Panel screens 4 In order to set a new p...

Страница 23: ...se damage to equipment or connected load Up to six power supplies of the same output voltage rating can be connected in parallel to provide up to six times the total output power capability of a singl...

Страница 24: ...lel Status screen and press Enter to move to the Parallel Settings screen 2 Scroll to the Parallel Mode setting and press Enter Scroll and choose a parallel mode setting then press Enter One unit must...

Страница 25: ...ly measure the output voltage of each power supply with the load connected then adjust the output voltage level of each power supply using the Intelligent Power Control interface on the front of the P...

Страница 26: ...SHARE B terminal on the second unit If there will be more than two units operating in parallel repeat this step for each unit as shown in Figure 4 above 5 Turn the Power Switch on all units to the ON...

Страница 27: ...el Send Secondary Alarm Emails If this box is checked while this power supply is operating as Primary unit the Primary will send out alarm notification e mails when an alarm occurs on a Secondary unit...

Страница 28: ...go to the Parallel Settings screen 5 Scroll to the Parallel Mode setting and press Enter Scroll and choose Standalone as the parallel mode setting then press Enter 6 The unit is now configured as a St...

Страница 29: ...icrosoft Internet Explorer Mozilla Firefox or Google Chrome 1 Start your Web browser 2 Enter the IP address of the power supply in the location address field of the browser If the power supply is conn...

Страница 30: ...30 3 Enter your user name and password The default Administrator user name is admin and there is no password by default 4 Once connected the System Status page will appear in your browser window...

Страница 31: ...tes the output status of the power supply The output ON OFF buttons will enable or disable the DC output and optional battery LVD contactor The Auto Restart button will disable the supply output for t...

Страница 32: ...rol tab to set all battery related parameters on units with the optional Battery LVD port SBC suffix units Click the Save Settings button after making changes to this page Output Voltage Control autom...

Страница 33: ...lize voltage setting recommended by the battery manufacturer Always consult with battery manufacturer and observe all battery manufacturer recommendations Equalize Voltage Set the Equalize charge volt...

Страница 34: ...nd time of the next Equalize charge if an Equalize Interval has been set Configure Battery The power supply will use this information to help determine the battery state of charge and remaining batter...

Страница 35: ...never the Battery Over current Alarm is triggered Battery Low SOC Alarm Set the battery low state of charge alarm threshold and actions here SOC Threshold Set the battery low state of charge alarm thr...

Страница 36: ...minutes for the Discharge Test Set Discharge Voltage Limit Set the minimum Discharge Voltage Limit If this Voltage Limit is hit before the Max Discharge Time limit the test will fail as the battery wa...

Страница 37: ...configured correctly before any e mail notifications can be sent DC OUTPUT FAILURE ALARM The alarm latches the output off and clears when the DC output is manually re enabled Activate Alarm Form C Con...

Страница 38: ...when an internal fan failure occurs and does not affect the power supply output state Activate Alarm Form C Contact If this box is checked the alarm form C contacts on the power supply will indicate...

Страница 39: ...ondary unit alarm e mails if desired See section 4 4 Advanced Parallel Operation with TCP IP Ethernet Operation for more information Parallel Mode Select Stand alone Primary or Secondary mode here to...

Страница 40: ...Click on the Download Log CSV button to store the CSV format log file on your computer for further analysis 5 5 Network Setup The NETWORK SETUP tab allows you to configure the network settings of the...

Страница 41: ...er The default HTTP port is 80 If you change the HTTP port to a number other than 80 you will have to append the new port number to the URL used to access the power supply e g http 192 168 0 180 8000...

Страница 42: ...o allow remote SNMP control of the power supply output If this box is unchecked all information available from the SNMP agent will be read only SNMP Contact Information Assign contact information such...

Страница 43: ...es is capable of sending email alarm notifications to multiple email addresses Configure these settings on the EMAIL SETUP tab if you would like to receive e mail alarm notifications from the power su...

Страница 44: ...f your SMTP server requires a user name and password enter the password here Leave this field blank if your SMTP server does not require authentication Minimum E mail Interval Specify a minimum interv...

Страница 45: ...onfirm New Password When changing a password you must re enter the new password here to confirm Administrator Password Enter the current Administrator password here to confirm changes 5 8 Maintenance...

Страница 46: ...his file Update the firmware on the power supply by clicking the Update Now button Do not remove AC power during the update process Send Test E Mail Pressing the Send Test E mail button will send test...

Страница 47: ...urrent IP address of the power supply can be found on the Network Status screen see the Control Panel Menus section for more information e Check Enable and then click on Save Settings NOTE Many ISP s...

Страница 48: ...ou may want to obtain a Static IP address from your ISP which will be more convenient to use to access the panel from a remote location A Static IP address is a fixed IP address that will not change A...

Страница 49: ...umber messaging nextel com Bell Mobility cellnumber txt bell ca Rogers cellnumber pcs rogers com Telus cellnumber msg telus com Virgin Mobile Can cellnumber vmobile ca 5 11 Network Troubleshooting I a...

Страница 50: ...t that the panel is connected to I am not receiving e mails from the power supply On the Communications Email Setup page ensure the SMTP Server field is the correct address for your e mail provider an...

Страница 51: ...Offline A unit connected to the RS485 bus has lost power A RS485 data cable has been unplugged or damaged A communications reset has been done to a unit connected to the RS485 bus The alarm will be c...

Страница 52: ...mperature Range 30 C to 70 C1 Storage Temperature 40 C to 70 C EMI Meets FCC part 15 and CE class B limits2 Safety Meets C UL EN 60950 1 standard Efficiency 90 93 typical Alarm Relay Form C 0 5A 125Va...

Страница 53: ...it adjustment range 25 120A 13 60A 10 60A 5 30A 5 30A 2 5 15A Default Output Current Limit 120A 60A 60A 30A 30A 15A Output V Noise mV rms 30 30 30 30 60 60 Input Current max at 100Vin rms 18A 16A 120V...

Страница 54: ...website at www ict power com support warranty repair The Purchaser shall at their own risk and cost return the defective product to ICT s factory or designated repair center once an RMA is issued by...

Страница 55: ...nmental conditions such as rust corrosive atmospheres sustained temperatures outside the specified operating range of the equipment exposure to power surges and or electrical surges improper grounding...

Страница 56: ...Helios Power Solutions Australia sales heliosps com au Middle East Asia sales heliosps asia New Zealand sales heliosps co nz...

Отзывы: