background image

 EN

4

Centrifugal fans – GigaBox GBW EC.. / GBD EC.. 

Installation and Operating Instructions 

2.0  Scope of delivery 

2.1  Accessories

 
2.2  Dimensions Unit

CHAPTER 2 

SCOPE OF DELIVERY AND 
ACCESSORIES

SDD-U

Anti vibration mounts 

for 

vibration-free installation 
indoors

(set of 4)

Ref.no. 5627 

GB-WK..

Wall bracket

for wall installation
  
 

Ref.no.

See catalogue

GB-WSD

..

Outdoor cover hood

for protected installation
outdoors   

Ref.no.

See catalogue

GB-WSG..

External weather louvres

for discharge side
 
 

Ref.no.

See catalogue

GB-KW..

Condensate collector

with outlet spigots for 
duct/hose connecti-
on 

See catalogue

ä

Standard parts:

ò

  GigaBox GB.. EC ... 

ù

  Outlet adapter, from square into circular  

(included in delivery)

ä 

Flexible sleeve 

GB-FM..

 

  (included in delivery)

Accessories:

ë 

External weather louvres 

GB-WSG..

 (accessories)

ö 

Outdoor cover hood 

GB-WSD..

 (accessories)

ü 

Anti vibration mounts 

SDD-U 

(accessories)

Å 

Wall bracket 

GB-WK..

 (accessories)

î 

Condensate collector with central outlet nozzle 

 

GB-RA..

 (accessories)

Fig.4

  GBD EC 710  A/B  1020  1020  710  250 

  GBW EC 250  

400  400  250  150

  GBW EC 315  

500  500  315  150

  GBW EC 355  

500  500  355  150

  GBW EC 400 A/B 

670  670  400  250

 

Type 

A  A 

Ø B 

C

  GBW EC 450  

670  670  450  250 

  GBD EC 450  

670  670  450  250 

  GBD EC 500  A/B 

800  800  500  250 

  GBD EC 560  

800  800  560  250 

  GBD EC 630  

1020  1020  630  250 

A

A

B

B

A

C

Fig.5

Dimensions in mm

The accessories are available in different sizes and 
designs. The corresponding Ref. no. can be found in the 
Helios sales documentation. 

The associated speed-potentiometers and the 
universal control system EUR EC are shown in the 
current EC-catalogue “EC greenVent - Ventilation in 
the future”.

m

 Outlet adapter is 

turned by 180° on deli-
very! Assembly carried 
out as shown in the 
picture.

ö

ü

ò

ù

î

Å

ä

ä

ë

Содержание GBD EC 450

Страница 1: ...tilatoren MONTAGE UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D UTILISATION EC Radialventilatoren EC Centrifugal fans Caissons centrifuges EC GigaBox GBW EC GBD EC DE EN FR ...

Страница 2: ...gsregelung Seite 2 1 17 Motorschutzeinrichtung Seite 3 KAPITEL 2 LIEFERUMFANG UND ZUBEHÖR Seite 4 2 0 Lieferumfang Seite 4 2 1 Zubehör Seite 4 2 2 Abmessungen Gerät Seite 4 2 3 Abmessungen Anschlussflansch Austritts Formstück Seite 5 2 4 Funktionsbeschreibung Seite 5 KAPITEL 3 AUFSTELLUNG MONTAGE Seite 5 3 0 Aufstellung Seite 5 3 1 Montage Seite 6 3 2 Demontage Seite 6 3 3 Elektrischer Anschluss S...

Страница 3: ... und Feuch tigkeitsindikatoren Der Lagerort muss erschütterungsfrei wassergeschützt und frei von übermäßigen Temperatur schwankungen sein Bei mehrjähriger Lagerung bzw Motorstillstand muss vor Inbetriebnahme eine Inspektion der Lager und gegebenen falls ein Lageraustausch durchgeführt werden Zusätzlich ist eine elektrische Prüfung nach VDE 0701 bzw VDE 0530 durchzuführen Bei Weiterversand vor alle...

Страница 4: ...men Der serienmäßige Klemmenkasten befindet sich auf der Motorträgerplatte bzw am Motor 1 14 Berührungsschutz m Bei Einbau sind die gültigen Arbeitsschutz und Un fall verhütungsvorschriften zu beachten Ein Be rüh rungs schutz gemäß DIN EN ISO 13857 ist sicherzustellen Kontakt mit rotierenden Teilen muss verhindert werden Es ist si cher zu stellen dass sich im Ansaug bereich keine Tex tilien oder a...

Страница 5: ... des Betriebs sowie ein Kurzschluss im Motor kann es zu einem Über stromfehler kommen Der Motor wird abgeschaltet Der Fehler wird über das Störmelderelais nach 10 s angezeigt Der Wiederanlauf des Ventilators ist nur über das Abschalten der Netzspannung für min 30 s möglich Netzunterspannung Fällt die Netzeingangsspannung 20 unter die jeweils spezifizierte Netzspannung wird der Motor abgeschaltet D...

Страница 6: ...EC 500 A B 800 800 500 250 GBD EC 560 800 800 560 250 GBD EC 630 1020 1020 630 250 Maße in mm Die Zubehörtteile sind in unterschiedlichen Größen und Ausführungen erhältlich Die entsprechende Bestell Nr kann den Helios Verkaufsunterlagen entnommen werden Die zu den EC Baureihen zugehörigen Drehzahl Po tentiometer und das Universal Regelsystem EUR EC können aus dem aktuellen EC Katalog EC greenVent ...

Страница 7: ...Type c A B c C D Ø E F G GBW EC 630 710 938 918 898 840 8 918 C B A E D F G Maße in mm C A D F E B GBW EC 250 450 GBW EC 500 710 Abb 6 Maße in mm Abb 7 3 0 Aufstellung Die GigaBox EC Baureihen ermöglichen eine flexi ble Aufstellung Einbaulage horizontal oder vertikal durch fünf mögliche axiale und radiale Ausblas richtungen des Austrittsformstücks siehe Abb 8 Auf eine sichere dauerhafte Befestigun...

Страница 8: ... Folgende Kontrollarbeiten sind auszuführen Bestimmungsgemäßen Einsatz des Ventilators über prüfen Die Baureihen dürfen nicht in explosionsgefährdeten Bereich betrieben werden Vor allen Wartungs und Installationsarbeiten oder vor Öffnen des Revisionsraumes ist das Gerät allpolig vom Netz zu trennen Der elektrische Anschluss darf nur von einer autorisierten Elektrofachkraft entspre chend den nachst...

Страница 9: ...ngsentkopplung zu anderen Bauteilen Gebäudeteilen haben Vibrationen und Schwingungen können verursacht werden durch ein unwuchtiges u U mit Schmutz beaufschlag tes Laufrad mangelhafte Entkopplung zum Rohrsystem oder Gebäudeteilen Stark geminderte Luftleistung kann auftreten bei falscher Drehrichtung wenn die sich einstellenden Rohrleitungs und Bauteil wider stände Gitter Klappen Filter usw höher a...

Страница 10: ... 8 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 976 GBD EC 450 500 A B 560 630 710 A B Drehstrom 3 400 V SS 973 GBW EC 250 GBW EC 315 GBW EC 355 GBW EC 400 A GBW EC 400 B GBW EC 450 Wechselstrom 1 230 V ...

Страница 11: ...7 2 Anschlusspläne mit PU A und EUR EC 9 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 974 SS 975 DE ...

Страница 12: ...10 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 977 SS 978 DE ...

Страница 13: ...11 Radialventilatoren GigaBox GBW EC GBD EC Montage und Betriebsvorschrift SS 1035 DE ...

Страница 14: ...ed control Page 2 1 17 Motor protection Page 3 CHAPTER 2 SCOPE OF DELIVERY AND ACCESSORIES Page 4 2 0 Scope of delivery Page 4 2 1 Accessories Page 4 2 2 Dimensions Unit Page 4 2 3 Dimensions Connecting flange outlet adapter Page 5 2 4 Functional description Page 5 CHAPTER 3 ASSEMBLY INSTALLATION Page 5 3 0 Assembly Page 5 3 1 Installation Page 6 3 2 Dismantling Page 6 3 3 Electrical connection Pa...

Страница 15: ...ion of motor by dry air dustproof packing plastic bags with drying agent and moisture indicators The storage place must be water proof vibration free and free of temperature variations When storing for several years or non rotation of motor an inspection of the bearings with possible relubrication and an electrical inspection to VDE 0701 and VDE 0530 are absolutely necessary before starting operat...

Страница 16: ... 1 is mandatory The rated voltage and frequency must be consistent with the information on the type plate The standard terminal box is located on the motor mounting plate or on the motor 1 14 Protection against accidental contact m When installing observe the valid regulations for labour protection and accident prevention A protection against accidental contact according to DIN EN ISO 13857 is to ...

Страница 17: ...blocking of the impeller during the operation as well as a short circuit in the motor an overcurrent error may occur The motor is switched off The error is displayed over the fail safe relay after 10 seconds The restart of the fan is possible only over switching the mains voltage off for min 30 s Mains undervoltage If the mains input voltage falls 20 under the mains voltage specified in each case ...

Страница 18: ...r louvres GB WSG accessories ö Outdoor cover hood GB WSD accessories ü Anti vibration mounts SDD U accessories Å Wall bracket GB WK accessories î Condensate collector with central outlet nozzle GB RA accessories Fig 4 GBD EC 710 A B 1020 1020 710 250 GBW EC 250 400 400 250 150 GBW EC 315 500 500 315 150 GBW EC 355 500 500 355 150 GBW EC 400 A B 670 670 400 250 Type c A A Ø B C GBW EC 450 670 670 4...

Страница 19: ...must be an interval of at least 120 seconds between activation and deactivation m In case of strong vibrations and or odours maintenance must be carried out by a specialist according to chapter 1 4 3 0 Assembly The EC GigaBox model range allows a flexible assembly installation position horizontal or verti cal by five possible axial and centrifugal dischar ge directions of the outlet adapter see Fi...

Страница 20: ...rear side 3 3 Electrical connection The following checks are to be carried out Check the intended purpose of the fan The series must not be operated in potentially hazardous atmospheres All maintenance and installation work must be carried out with the equipment fully isolated from the power supply The electrical connection is to be carried out in accordance with the relevant wiring diagram and is...

Страница 21: ...o high Abnormal noises can be caused by incorrect direction of rotation worn out ball bearings lack of vibration decoupling to other buildings and ducting systems Vibrations and oscillation can be caused by unbalanced or dirty impellers lack of vibration decoupling to other buildings and ducting systems Extreme reductions in performance can occur in case of incorrect direction of rotation if resis...

Страница 22: ...stallation and Operating Instructions 7 1 Standard wiring diagram SS 976 GBD EC 450 500 A B 560 630 710 A B rotary current 3 400 V SS 973 GBW EC 250 GBW EC 315 GBW EC 355 GBW EC 400 A GBW EC 400 B GBW EC 450 Alternating current 1 230 V Terminal box ...

Страница 23: ...l fans GigaBox GBW EC GBD EC Installation and Operating Instructions EN 7 2 Wiring diagram with PU A and EUR EC SS 974 SS 975 Terminal box Example EUR EC control EC Motor SS 973 with modus 4 01 pressure controlled ...

Страница 24: ...10 Centrifugal fans GigaBox GBW EC GBD EC Installation and Operating Instructions SS 977 SS 978 Example EUR EC control EC Motor SS 976 with modus 4 01 pressure controlled EN ...

Страница 25: ...11 Centrifugal fans GigaBox GBW EC GBD EC Installation and Operating Instructions SS 1035 EN ...

Страница 26: ...1 17 Protection moteur Page 3 CHAPITRE 2 CONTENU DE LA LIVRAISON ET ACCESSOIRES Page 4 2 0 Contenu de la livraison Page 4 2 1 Accessoires Page 4 2 2 Dimensions Page 4 2 3 Dimensions des pièces de raccordement Page 5 2 4 Description des fonctionnalités Page 5 CHAPITRE 3 INSTALLATION MONTAGE Page 5 3 0 Installation Page 5 3 1 Montage Page 6 3 2 Démontage Page 6 3 3 Raccordement électrique Page 6 CHA...

Страница 27: ...à l air et la poussière sac en matière synthétique contenant des sachets deshydrateurs et un indicateur d humidité Le matériel est à stocker dans un endroit abrité de l eau exempt de variations de températures et de vibrations En cas de stockage sur plusieurs années entraînant une immobilisation du moteur il faut effectuer un contrôle des roulements et éventuellement les changer avant la mise en s...

Страница 28: ...e aux indi cations de l étiquette La boîte à bornes livrée de série se trouve sur la plaque support moteur ou directement sur le moteur 1 14 Protections m Lors de l installation respecter les instructions en vigueur relatives au Code du Travail et à la prévention des accidents Il faut prévoir toutes les protections nécessaires conformément à la norme DIN EN ISO 13857 Toute possibilité de contact a...

Страница 29: ...du rotor pendant son fonctionnement ou un court circuit dans le moteur peuvent entraîner une surintensité Le moteur se coupe La défaillance sera signalée au relais de signalement des défauts après 10 secondes Le redémarrage du ventilateur n est possible qu après une coupure de la tension du secteur d une durée minimum de 30 secondes Sous tension du réseau Si la tension du réseau tombe 20 en dessou...

Страница 30: ... antivibratoires SDD U acc Å Console murale GB WK acc î Bac de récupération des condensats avec écoulement central GB RA acc Fig 4 GBD EC 710 A B 1020 1020 710 250 GBW EC 250 400 400 250 150 GBW EC 315 500 500 315 150 GBW EC 355 500 500 355 150 GBW EC 400 A B 670 670 400 250 Type c A A Ø B C GBW EC 450 670 670 450 250 GBD EC 450 670 670 450 250 GBD EC 500 A B 800 800 500 250 GBD EC 560 800 800 560...

Страница 31: ...ores procéder à une maintenance selon les consignes de la section 1 4 3 0 Installation Les séries GigaBox EC permettent de nombreuses possibilités d installation et de montage horizon tale et verticale grâce aux cinq emplacements possibles de la pièce de transformation voir fig 8 Veiller à fixer l appareil de façon solide et durable et garantir un accès aisé à la boîte à bornes et à l unité moto t...

Страница 32: ...res composants de l installation 3 3 Raccordement électrique Les vérifications suivantes sont à réaliser Vérifier que l utilisation du ventilateur est conforme à la prescription Cette gamme ne doit pas être utilisée dans des zones à risque d explosion Mettre impérativement l appareil hors tension avant tous travaux d entretien de réglages ou l ouverture de la trappe de visite Le branchement électr...

Страница 33: ...Le ventilateur doit tourner de façon centrifuge à toutes les vitesses 5 0 Nettoyage et entretien Les travaux de maintenance et d entretien ne doivent être effectués que par des professionnels qualifiés et expérimentés et conformément aux dispositions et réglementations en vigueur m S assurer que l appareil est hors tension avant toute intervention et qu il est bloqué en position arrêt grâce à l in...

Страница 34: ...nal 0 10 V SS 976 GBD EC 450 500 A B 560 630 710 A B Triphasé 3 400 V SS 973 GBW EC 250 GBW EC 315 GBW EC 355 GBW EC 400 A GBW EC 400 B GBW EC 450 Monophasé 1 230 V Code couleur selon CEI 757 BK noir BN marron RD rouge OG orange YE jaune GN vert BU bleu VI violet WH blanc Valable à partir des versions 5810 002 et 5811 002 Alimentation 1 6 mA max Alimentation 2 20 mA max Valeur de consigne ouvert q...

Страница 35: ...uge OG orange YE jaune GN vert BU bleu VI violet WH blanc Exemple Régulateur EUR EC pour moteur EC SS 973 en mode 4 01 pression Signalisation Relais sonde Câbles de commande 30 m max à partir de 20 m blindés voir notice de montage et d utilisation Paramétrage EUR EC Entrée sonde E1 paramétrage usine mode 4 01 pression Sortie analogique A1 IO Setup Fonction A1 2A contrôle proportionnel Signalisatio...

Страница 36: ...pour sélection sonde sonde Paramétrage EUR EC Entrée sonde E1 paramétrage usine mode 4 01 pression Sortie analogique A1 IO Setup Fonction A1 2A contrôle proportionnel Signalisation des défauts via entrée numérique D1 IO Setup Fonction D1 2D défaut externe D1 inversion enclenchée Autorisation via relais K1 IO Setup Fonction K1 1K message fonctionnement Sonde de pression N Réf 1322 Câbles de command...

Страница 37: ...e charge potentiomètre charge tous les ventilateurs Principe de raccordement Commande de plusieurs ventilateurs EC avec PU PA sans LED Principe de raccordement Commande de plusieurs ventilateurs EC avec PU PA avec LED Ventilateur EC n 1 Ventilateur EC n 2 Ventilateur EC n 3 Ventilateur EC n 1 Ventilateur EC n 2 Ventilateur EC n 3 Attention Le branchement en parallèle de la tension 10 V DC n est pa...

Страница 38: ...12 ...

Страница 39: ...13 ...

Страница 40: ...nstraße 4 8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensstraße 15 6023 Innsbruck Colchester Essex CO4 9HZ www heliosventilatoren de Als Referenz am Gerät griffbereit aufbewahren Druckschrift Nr Please keep this manual for reference with the unit Print No Conservez cette notice à proximité de l apapre...

Отзывы: