Cooling register AIR1-KR DX
Installation and Operating Instructions
14
4. Attach the cooling register to the unit. Connect the free temperature sensor plug from the unit to the cooling register
5. Screw the cooling register and the unit together (Screw: M8 x 16; s. Fig.15).
6. Connect the cooling register to the flow and return pursuant to local regulations.
7. Cooling can produce condensate. The correct condensate connection to the sewage system must be ensured
before commissioning. A siphon or condensate pump is required for this purpose. The condensate must drip freely
into the drain after the siphon or condensate pump.
2�7�2 Cooling register DX for AIR1 XH and RH units
1. Apply sealing strips where the cooling register is joined together with the AIR1 unit or the external auxiliary heater
3. Remove the temperature sensor from the supply air side of the AIR1 unit or the external auxiliary heater. Then attach
Fig�14
Fig�15
Fig�16
Fig�17