Cooling register AIR1-KR DX
Installation and Operating Instructions
12
When using the cooling register below, the corresponding AIR1 XC unit must be suspended lower from the ceiling (see
table,Fig.9).
– for ventilation units AIR1 XH and RH
When installing the unit, the following criteria must be observed when installing the unit to ensure easy accessibility for
maintenance and maintenance work (Fig.10).
A:
Minimum distance for servicing the cooling register.
– Ensure that the multi-leaf dampers are installed for frost protection�
– Cooling registers XH and RH are only suitable for outdoor installation in combination with the corresponding
weather protection covers AIR1-AAD KR KW and DX!
– The terminal box with the control system connection is only suitable for indoor installation�
Type
H (mm)
AIR1-KR DX XC 700
35
AIR1-KR DX XC 1400
40
Fig�9
H
Fig�10
Type
A (mm)
AIR1-KR DX XH 1000
985
AIR1-KR DX XH 1500
995
AIR1-KR DX XH 2500
1215
AIR1-KR DX XH 3500
1375
AIR1-KR DX XH 4500
1425
AIR1-KR DX XH 5500
1635
AIR1-KR DX XH 7000
1935
AIR1-KR DX XH 8500
2285
Type
A (mm)
AIR1-KR DX RH 1500
960
AIR1-KR DX RH 2000
1060
AIR1-KR DX RH 3000
1170
AIR1-KR DX RH 5000
1440
AIR1-KR DX RH 6000
1560
AIR1-KR DX RH 8000
1810
AIR1-KR DX RH 9500
1910
AIR1-KR DX RH 12000
2060
AIR1-KR DX RH 15000
2310
NOTE