background image

Installation Instructions

Optical Smoke Switch ORS 142

Connecting the relay contacts:

4
5

in operation

- slight contamination

- heavy contamination

4
5

- power failure
- fault
- alarm

4.3 Installing the Smoke Switch

  Install the Smoke Switch only when the 

power supply is switched off!

The Smoke Switch is fitted directly in its base, as 
shown in the illustrations below:

�����

Please see Section 8 “Ordering data” for the bases 
available for mounting Smoke Switch ORS 142.

5 Testing the Smoke Switch

After installation, the Smoke Switch must be tested 
for correct operation using the test aerosol. When 
carrying out tests, be sure to follow the safety in-
structions printed on the can of Test Aerosol 918/5.

6 Maintenance instructions

The LED display provides a permanent indication of 
the operational status of the Smoke Switch. To avoid 
false alarms, when the LEDs signal “heavy contami-
nation”, replace the Smoke Switch or send it for 
servicing in our works.

6.1 Meanings of LED signals

����

Signal, 

frequency

LED colours Meaning

Green

In operation

Green/yellow Slight contamination
Green/yellow Heavy contamination
Yellow

Fault

Red

Alarm

“Off”

Power failure

7 Technical data for ORS 142

Switches off due to overheating ca. 70°C
Operating voltage

18 V DC ... 28 V DC

Current draw at 28 V DC

 

Quiescent

 

Alarm condition

 

Fault condition

max. 21 mA

max. 10 mA

max. 25 mA

Relay contacts

 

Switched voltage

 

Switched current

 

Switched power

max. 30 V DC

max. 1 A

max. 30 W

Protection rating

IP 42

Ambient temperature for 

operation

-20 °C ... +60 °C

Weight

120 g

8 Ordering data

Product designation, description

Order no..

Smoke Switch ORS 142

5000552

Heat Switch TDS 247

5100158

Base 143 A for surface mounting on ceilings 5000350
Base 143 W for surface mounting on walls

5000513

Base 143 AF for surface mntg. in damp 

areas

5000356

Base 143 UH for flush mounting in ceilings

5000359

Mains NG 519

230 V AC / 24 V DC, 350 mA

5400080

Mains unit NAG 03

230 V AC / 24 V DC, 900 mA

5400081

Test aerosol 918/5

6900331

A member of the

Securitas Group Switzerland

HEKATRON Vertriebs GmbH

Brühlmatten 9

D-79295 Sulzburg

T49 (0) 76 34  500-3 10

T49 (0) 76 34  500-3 23

www.hekatron.com

[email protected]

click

7002283 030206.VDA

Specififcations subject to change without 

notice. Delivery subject to availability.

Z-6.5-1725