PRIAMOS I
11
5.2.3
Tooth Profile
Any tooth profile is admissible. The top width of the tooth should be 2.5 mm minimum,
the gap and the depth of the gap at least 4 mm (8 mm at IA 22 - 76 and IA 23 - 102).
For index plates the same dimensions are valid.
Due to tolerances, a radial arrangement of the magnetic pickup is preferable.
5.2.4
Clearance for IA 02 - 76 up to IA 13 - 102
The distance between the magnetic pulse pickup and the tooth top should range from
0.5 to 0.8 mm. (It is possible to screw in the magnetic pickup till it touches the tooth and
then unscrew it for about half a turn.)
5.2.5
Clearance for IA 22 - 76 and IA 23 - 102
The distance between the magnetic pulse pickup and the tooth top should range from
2.5 to 3 mm. (It is possible to screw in the magnetic pickup till it touches the tooth and
then unscrew it for about two turns.)
Figure 2: Clerance of Pickup