background image

INSTALLATION INSTRUCTIONS

Fan Coils: FEM4X, FEM4P, REM4X, FXM4X

496 01 5503 02

11

Specifications  are subject to change without notice.

REFRIGERANT FLOW

CONTROL DE-

VICE

FEM4P Models:

These units come equipped with a 

factory installed Piston

metering device with Teflon ring

. If a piston replacement is

required, check piston size shown on indoor unit rating plate

to see if it matches required outdoor piston size. The outdoor

piston size will be found on the outdoor unit rating plate,

product data or installation instructions depending on the

model shown on outdoor unit rating plate. If the fan coil piston

does not match, replace indoor piston with correct outdoor

piston. With some outdoor units a piston is shipped with

outdoor unit.
When changing piston, use a back

up wrench. Hand tighten

hex nut, then tighten with wrench 1/2 turn. Do not exceed 30

ft

lbs.

NOTE: 

The indoor piston contains a Teflon ring (or seal)

which is used to seat against the inside of distributor body,

and must be installed properly to ensure proper seating in the

direction for cooling operation.
Always use outdoor units designed to match indoor fan coil

applications.

REFRIGERANT METERING DEVICE

FEM4X, REM4X, FXM4X Models:

These Fan Coils have a factory installed hard shut

off TXV

designed only for use with R

410A refrigerant. Use only with

outdoor units designed for R

410A.

TXV is factory set and not field adjustable.

!

CAUTION

PRODUCT DAMAGE HAZARD

Failure to follow this caution may result in product

damage.
This Fan Coil has a hard shut

off TXV metering device. A

compressor  Hard Start Kit is REQUIRED in all

applications where the matching outdoor unit has a

single

phase reciprocating compressor.

!

CAUTION

PRODUCT OPERATION HAZARD

Failure to follow this caution may result in improper prod-

uct operation.

If using a TXV in conjunction with a single

phase recipro-

cating compressor, a compressor start capacitor and relay

are required. Consult outdoor unit pre

sale literature for

start assist kit part number.

Figure 15

Refrigerant Flow

Control Device

TEFLON SEAL

BRASS

HEX NUT

STRAINER

PISTON
RETAINER

BRASS
HEX BODY

DISTRIBUTOR

PISTON

FLOW IN
COOLING

TEFLON RING

CONDENSATE DRAINS

Unit is provided with primary and secondary 3/4

” (19mm)

NPT drain connections. Refer to 

Figure 2

Figure 3

,

Figure 4

Figure 5

, and 

Figure 6

 to identify the primary and

secondary locations. To prevent property damage and

achieve optimum drainage performance, BOTH primary and

secondary drain lines should be installed and include

properly sized condensate traps (refer to 

Figure 16

).

Factory approved condensate traps are available (accessory

part number EBAC01CTK).
To connect drainlines, the drain connection knock

outs must

be removed. Use a knife to start the opening near the tab and

using pliers, pull the tab to remove the knock

out. Clean the

edge of the opening if necessary. After drain fittings are

installed, caulk the seam between the fitting and the cover to

retain the low leak rating of the unit.
It is recommended the PVC fittings be used on the plastic

condensate pan. Do not over

tighten. Finger

tighten plus

1

1/2 turns. Use pipe dope to ensure proper seal.

Install traps in the condensate lines as close to the coil as

possible (refer to 

Figure 18

), but avoid blocking filter access

panel.
Install drain lines below the bottom of the drain pan and pitch

the drain lines down from the coil at least 1/4 inch per foot of

run (6mm per 0.3m). Horizontal runs over 15 feet (5m) long

must also have an anti

siphon air vents (stand pipes),

installed ahead of the horizontal runs. Extremely long

horizontal runs may require oversized drain lines to eliminate

air trapping.
Route primary drain line to the outside or to a floor drain.

Check local codes before connecting to a waste (sewer) line.
Route the secondary drain line to a place in compliance with

local installation codes where it will be noticed when unit is

operational. Condensate flowing from secondary (overflow)

drain indicates a plugged primary drain 

 unit requires

service or water damage will occur.

Содержание FEM4P

Страница 1: ...in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or picture...

Страница 2: ...ly duct work NOTE If the door gasket is damaged or missing the unit may not meet the ASHRAE 193 standard for cabinet air leakage Contact your supplier and order kit 1191140 Nuisance sweating may occur...

Страница 3: ...REM36 17 432mm FXM30 19 483mm B MODULAR UNITS FEM4X6000B REM4X6000B and FXM4X4800 6000 fan coils are two piece modular units This allows for modular units to be disassembled and components moved sepa...

Страница 4: ...kaged with accessory kit See Product Specification literature for kit part numbers During the conversion process remove the plastic cap covering the vertical drains only and discard Remove the plug fr...

Страница 5: ...fitting panel refer to Figure 5 2 Remove coil mounting screw securing coil assembly to right side casing flange 3 Remove coil assembly 4 Lay fan coil unit on its right side and reinstall coil assembly...

Страница 6: ...ghs C and install on opposite tube sheets f Install hose onto plastic spout 7 Install horizontal pan on right side of coil assembly 8 Slide coil assembly into casing Be sure coil bracket on each corne...

Страница 7: ...NST WALL 1 8 3mm INCH THICK ANGLE MOUNTING BRACKET TYPICAL BOTH SIDES SECURE FAN COIL TO STRUCTURE UNIT AWAY FROM WALL PIPE STRAP SECURE UNIT TO FLOOR ANGLE BRACKET OR PIPE STRAP 4 102mm MAX 4 102mm M...

Страница 8: ...rmed until the main disconnect switch remote to the unit is turned off A LINE VOLTAGE CONNECTIONS Fan Coils installed without electric heat require the use of a factory authorized Power Plug Kit acces...

Страница 9: ...uninterrupted or unbroken ground in order to minimize potential for personal injury or death if an electrical fault should occur The ground may consist of electrical wire or metal conduit when instal...

Страница 10: ...it bottoms 3 Braze connection using silver bearing or non silver bearing brazing materials Do not use solder materials which melt below 800_F 427_C Consult local code requirements 4 Evacuate coil and...

Страница 11: ...equired Consult outdoor unit pre sale literature for start assist kit part number Figure 15 Refrigerant Flow Control Device TEFLON SEAL BRASS HEX NUT STRAINER PISTON RETAINER BRASS HEX BODY DISTRIBUTO...

Страница 12: ...w running traps are inadequate and DO NOT allow proper condensate drainage refer to Figure 17 Figure 16 Recommended Condensate Trap 2 MIN 51mm 2 MIN 51mm UNIT Figure 17 Insufficient Condensate Trap DO...

Страница 13: ...r motor is de energized and stops E ELECTRIC HEAT OR EMERGENCY HEAT MODE Thermostat closes R to W W energizes electric heat relay s which completes circuit to heater element s W also energizes the ind...

Страница 14: ...4200 Tap 5 1560 1544 1507 1464 1424 1358 Tap 4 1419 1397 1358 1320 1279 1239 Tap 3 1419 1397 1358 1320 1279 1239 Tap 2 1249 1220 1184 1142 1093 1052 Tap 1 1242 1205 1158 1110 1069 1026 4800 Tap 5 1743...

Страница 15: ...1294 1245 Tap 2 1257 1226 1191 1141 1090 1033 Tap 1 1237 1206 1160 1121 1070 1013 FXM4X4800 Tap 5 1757 1725 1693 1653 1614 1576 Tap 4 1664 1626 1593 1552 1517 1477 Tap 3 1664 1626 1593 1552 1517 1477...

Страница 16: ...049 0 059 FXM4X24 0 016 0 027 0 038 0 049 0 059 30 0 049 0 059 0 070 0 080 36 0 070 0 080 0 090 0 099 FXM4X36 0 055 0 064 0 073 0 081 42 0 049 0 056 0 063 0 070 48 0 063 0 070 0 076 0 083 0 090 FXM4X...

Страница 17: ...ere POE oils may cause damage to certain plastics and roofing materials Vacuum pumps will not remove moisture from oil A liquid line filter drier is required on every unit Do not use liquid line filte...

Отзывы: