10.3.9 Overheat Protection For Discharge Temperature
Outdoor display: LED1 flash 8 times
Method of The Discharge temperature control is checked with the temperature being detected
Malfunction by the Discharge pipe thermistor
●
Detection
Malfunction when the compressor discharge temperature is above 110
℃
Decision
Conditions
Supposed ■ Electronic expansion valve defective
●
Causes ■ Faulty thermistor
■ Faulty PCB
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Electrify the machine again and turn it on with the remote controller,
then measure the temperature at the exhaust temperature sensor of
the compressor on the outdoor unit
The temperature exceeds
110
℃
shortly after the
machine starts up?
●
1) The cryogen may have been leaked during
installation, or there may be leakage in the piping
system.
2) There may be other causes to make the exhaust
temperature too high.
Malfunctions occur after running for some time even
●
though the measured temperature is below 110
℃
. Pull
out the exhaust sensor and measure its resistance at
standard
temperatures
according
to
the
resistance-temperature table
The
results
deviate
much?
The sensor is damaged. Replace the sensor
with a new one.
The outdoor mainboard is damaged and needs be
●
replaced
YES
NO
NO
YES
Содержание 2P Series
Страница 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV...
Страница 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40...
Страница 30: ...Dimensional drawing 28 Domestic air conditioner 8 Dimensional drawings 9 Center of gravity...
Страница 38: ...Service diagnosis 36 Domestic air conditioner...
Страница 60: ...Sincere Forever...