Functions and control
17
Domestic air conditioner
If |SH|
≥
3,and
△
SH=0, 10s/ 1 step.
If 3
≥
|SH|
≥
0, 30s/ 1 step.
△
SH= current SH- last SH
SH= Ts (suction temp)-Tc1 (indoor coil temp)-Tsh (fixed data, depend on different models, -1~2)
7.1.4 Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the
four-way valve.
7.1.5 Protection function
7.1.5.1 TTC high temperature-preventing protection
Once the machine is started, it can run TTC(air-blowing temp)
overheating protection of
air-blowing, but air
●
-blowing sensor malfunction must alarm after 4 minutes during which the
compressor is started (during the course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the mean
value of the middle 2 values), take the mean value.
TTC
(℃)
Abnormal stop
107
Decreasing the frequency rapidly
(
1HZ/second
)
104
Decreasing the frequency slowly (1HZ/10seconds)
100
The frequency doesn’t change.
98
Increasing the frequency (1HZ/10second)
●
93
Increasing the frequency
●
(
1HZ/1second
)
TTC>=1
●
07
℃
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
7.1.5.2 TC high temperature-preventing control of the indoor heating unit
:
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the
running state). TC=indoor coil temp.
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
●
temperature is higher than 63
℃
, decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat
exchanger is lower than 45
℃
, recover to the normal control.
Содержание 2P Series
Страница 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV...
Страница 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40...
Страница 30: ...Dimensional drawing 28 Domestic air conditioner 8 Dimensional drawings 9 Center of gravity...
Страница 38: ...Service diagnosis 36 Domestic air conditioner...
Страница 60: ...Sincere Forever...