Heater wiring schematic diagrams 

 

It is recommended to install an ON/OFF isolation switch before the controller and ensure the unit is turned OFF after use. 
 
As the minimum current rating for THX is 10Amps (THX2400), only 1 heater can be directly wired to the controller.  

 

When more heating units need to be connected from the same controller a relay will be required. It is recommended that 
you talk to your electrician for more detail.  
 
 
Below are example circuits indicating potential installation configurations. 
Always check with your electrician and ensure all wiring is in accordance with local regulations. 

 

Note to electrician: The controller modulates the heat output using a “timed on / timed off” function. The controller does not 
modulate the voltage output. A relay is therefore suitable for this application.  

Содержание Max THX 3600

Страница 1: ...OPERATION INSTALLATION AND MAINTENANCE MANUAL HEATSTRIP Max The heater that is a design feature ...

Страница 2: ...ted outdoor smoking and leisure areas as well as for workstation spot heating in factories warehouses and showrooms Within your home HEATSTRIP can provide comfort heating for undercover alfresco dining and BBQ area patios verandas courtyards and balconies APPLICATION THS THH THX Indoor insulated areas classrooms offices bathrooms wet areas drying rooms X Outdoor under cover café veranda patio balc...

Страница 3: ...eded For outdoor applications the Heatstrip Max is suitable for both permanently exposed eg courtyards and patios and undercover installations does not need to be fully protected from the elements High Strength element virtually indestructible The unique metallic Incoloy element is 14mm thick meaning it is vandal proof and will not shatter like other glass quartz heating elements Provides piece of...

Страница 4: ...minal at 50 60 Hertz Single Phase CONNECTION 3 Core Cable 2 5mm2 APPROVALS AUSTRALIA NZ MOUNTING HEIGHT MINIMUM RECOMMENDED MAXIMUM 2 1 m 2 4 m to 3 0 m 3 5 m For higher ceiling heights units can be lowered using optional bracket kits or refer to the Heatstrip Max range MOUNTING OPTIONS Suitable for ceiling wall beam mounting Also available for extension mount using rigid fixing poles and chain mo...

Страница 5: ...h as over outdoor tables BBQ s lounges assembly lines or indoor workstation Often it is more practical and efficient to spot heat these areas Spot heating will help to reduce the initial capital cost as well as the running costs Spot heating will allow the area to be zoned meaning heating only the areas that are being used such as tables in a restaurant or outdoor alfresco area The top table shows...

Страница 6: ...ly under the heater and the temperature decreases as you move away from the heater It highlights the importance of maintaining recommended mounting heights and positioning the heater directly above the area to be heated if possible Also the temperature ie surface temperature is the same for both models regardless of the wattage However the size increases and the length of the unit increases the ra...

Страница 7: ...etc HEATSTRIP Indoor THS models is a medium intensity heater used for protected indoor applications such as sunrooms school classrooms halls gymnasiums etc General recommendations for HEATSTRIP Max Ideal mounting height 2 4m to 3 5m Maximum is 3 5m in a protected outdoor environment Ideal mounting location ceiling mounted directly above area to be heated eg above a table Based on the radiant footp...

Страница 8: ...s more than 3 5m we recommend the use of the optional accessories to reduce the height of the heater to 2 4m 3 5 m This will increase the effectiveness of your HEATSTRIP Refer to the Mounting Accessory section for more information Electrical connections GPO s should not be located at the back of the heater They should be located outside the physical footprint of the units to minimize heat build up...

Страница 9: ...TER CEILING FLOOR SURFACE BELOW HEATER 300mm MIN 150mm MIN 150mm MIN 2100mm MIN 1000mm MIN Angled Ceiling Installation Ceiling Installation 150mm MIN 150mm MIN 300mm MIN LIGHT OR SPRINKLER MUST NOT BE BELOW THE HEATER CEILING FLOOR SURFACE BELOW HEATER 1000mm MIN 2100mm MIN Installation location the below diagrams confirm the minimum recommended clearances Angled Wall Installation ...

Страница 10: ...ins or poles attached to beams or poles or 2 units together Refer to the following pages for more detailed information on each mounting option STANDARD MOUNTING BRACKETS INCLUDED IN BOX BEAM MOUNT WITH STANDARD BRACKET END TO END MOUNTING BRACKET SUSPENSION MOUNTING WITH STANDARD BRACKET EXTENSION MOUNT KIT WITH POLES TWIN MOUNTING BRACKETS FLUSH MOUNT ENCLOSURE CEILING TWIN MOUNT BRACKET STANDARD...

Страница 11: ...suspend with chains The brackets need to be mounted onto a secure frame or wall with a minimum distance between the two brackets The minimum distance B for each model is listed in the table below When completing the installation ensure all screws are tight and unit is secure Note When suspension mounting chains are not included PART No PACKAGED DIMENSIONS mm WEIGHT kg MATERIALS ZBRAK 104 125 x 100...

Страница 12: ... the L brackets to the threaded connectors in the required locations on rear of heater to match the centres of the mounting brackets Lift heater into position and secure the mounting brackets to the L brackets using the screws provided Locate the C cutout on the L bracket onto the stud in the mounting bracket so you achieve either horizontal or angle mounting position as required Tighten all screw...

Страница 13: ...a maximum ceiling height of 3 5m in an outdoor environment Maxi mum mounting heights should be strictly followed otherwise the performance of the units may be reduced The facia of the enclosure is manufactured from 316 Stainless Steel and the rear casing is black zinc coated steel Please refer to the Installation Manual for more detailed installation information SUITABLE FOR MODELS PART No HOLE CU...

Страница 14: ...ional Twin Mount bracket allows for two 2 units of HEATSTRIP Max to be mounted side by side either in parallel or angled as per the diagram on the right This is ideal for applications when a wider heat coverage is required or when there is mounting restrictions limitations such as running between 2 rows of tables etc ...

Страница 15: ...d aesthetic appeal This is ideal for applications such as long rows of tables and assembly lines where a constant heat coverage is required The bracket allows for a 50mm gap between units and an opening for the power connection As per the dia gram below units should be mounted with the power leads together The end to end bracket can be used with either the standard ceiling wall mount bracket or th...

Страница 16: ...6 SS Kit includes 2x1200mm extension pole screws and brackets The Extension Mount bracket allows HEATSTRIP Max units to be lowered from high ceilings using rigid con nections The brackets are for use with 25mm x 25mm x 1mm tube SHS supplied as a complete kit with brackets pre cut poles and connections The standard length options as part of the kit are 300mm 600mm 900mm and 1200mm The kits include ...

Страница 17: ...ower The heater needs to be installed as per the installation instructions paying special attention to the minimum clearances The heater needs to be mounted on a rigid bracket or fixing The heater must not be mounted immediately below or in front of a socket outlet In case of a heater fault or damaged supply lead the appliance should be returned to the point of purchase for return to Thermofilm fo...

Страница 18: ...ces the likelihood of heaters being inadvertently left turned on Depending on the ambient temperature there may be a requirement to control the heat output of the heater The controller has 3 settings they are High Medium and Low The controller allows a combination of the multiple timer 1 2 4 hour and heat outputs High Medium Low The controller comes with a remote control unit which provides conven...

Страница 19: ...e connected from the same controller a relay will be required It is recommended that you talk to your electrician for more detail Below are example circuits indicating potential installation configurations Always check with your electrician and ensure all wiring is in accordance with local regulations Note to electrician The controller modulates the heat output using a timed on timed off function ...

Страница 20: ...ce of an examination of the faulty product or components by Thermofilm or an authorized representative of Thermofilm Thermofilm does not participate in any site related costs or labour expenses incidental to replacement of parts repairing removing installing servicing transportation or handling of parts to complete products and assumes no liability on parts repaired or replaced without written aut...

Отзывы: