Megalife Product Guide

8

5: Installation - Auxillary Coil (Indirect Units)

5.1 Boiler Selection

The Auxillary coil on the Megalife solar indirect models are suitable for use with most gas, oil or electric boilers. The 
boiler used can either be a sealed system or open vented type. The maximum primary circuit pressure is 3.5 bar. If 
an open vented type boiler is used it must be fed from a separate boiler feed and expansion cistern, it MUST NOT 
be fed from the Megalife solar cold water feed cistern.

The auxilary primary flow from the boiler 

MUST

 be pumped. Gravity circulation will not work due to the special design 

of the primary heat exchanger. It is recommended that an air bleed point or automatic air vent is incorporated in the 
primary return pipework close to the Megalife solar unit to aid in bleeding air from the primary heating coil.

The boiler should be fitted with adequate thermal control. This will normally include a primary flow thermostat and a 
safety over temperature cut-out. The boiler flow temperature should usually be set to 82

o

C (maximum flow temperature 

to primary heat exchanger 90

o

C).

The boiler cannot be vented through the Megalife solar unit.

5.2  Indirect Thermal Controls

Control of the storage temperature when indirectly heated is provided by the fitted cylinder thermostat. The control is 
located under the white plastic cover located to the right of the indirect coil connections. If necessary the temperature 
can be adjusted by inserting a flat bladed screwdriver in the adjustment knob and rotating. The minimum thermostat 
setting is 10°C. Adjustment represents a temperature range of 10°C to 72°C (See Fig. 05, page 9). If in any doubt 
contact a competent electrician.

5.3 Wiring

All electrical wiring should be carried out by a competent electrician and be in accordance with the latest I.E.E. 
Wiring Regulations.
The Megalife solar indirect thermostat and thermal cut-out are factory pre-wired. It is recommended that these controls 
are wired in series with a suitable 2 or 3 port motorised valve to control the primary flow through the heater coil. Wiring 
to external controls is made via the terminal block fitted. The cable should be routed through the aperture in the 
terminal cover and secured using the cable grip provided. The indirect thermal cut-out 

MUST NOT

 be bypassed.

5.4 Heating System Controls

The controls provided with the Megalife solar will ensure the safe operation of the Megalife solar when heated 
by an auxillary heat source. Additional controls will be required for the control of the solar primary heating circuit. 
Other controls will be necessary to control the space heating requirements and times that the system is required to 
function. Depending on the auxillary boiler selected, heating circuit design and controls used it may be beneficial 
to incorporate a system by-pass in the auxillary heating system pipework.
 
The Megalife solar is compatible with most heating controls, examples of electrical circuits are given in Fig’s 06 and 
07, page 10. However, other systems may be suitable, refer to  the controls manufacturers’ instructions, supplied with 
the controls selected, for alternative system wiring schemes.

5.5 Immersion Heater

The Megalife solar indirect units are supplied with an immersion heater which can be used as an alternative heat 
source should the boiler supply need to be isolated from the Megalife solar unit. Refer to Fig. 05 page 9 for details 
of the wiring and operation of the immersion heater.

36005941_issue_07.indd   8

07/09/2017   08:40:33

Содержание Megalife CLV190

Страница 1: ...Megalife Solar Vented Cistern Fed Water Heater Installation manual SOLAR DIRECT 36005941_issue_07 indd 1 07 09 2017 08 40 29...

Страница 2: ...tlet that is arranged to discharge over the cold water feed cistern The Megalife solar water heaters are supplied with a dedicated solar coil in the lower part of the cylinder which must be connected...

Страница 3: ...hot water from the safety devices to an appropriate place open to atmosphere where it will cause no danger to persons in or about the building Vented hot water storage systems 3 12 Vented hot water s...

Страница 4: ...ously Water Byelaw 30 A vent pipe MUST be connected to the outlet of the heater This must rise continuously and be arranged to discharge into the feed cistern The vent pipe must have a minimum bore di...

Страница 5: ...lly the pipework from the heater to the outlet fittings should be in 22mm pipe with short runs of 15mm pipe to the terminal fittings Pipe sizes may vary due to system design 3 5 Vent Pipe A vent pipe...

Страница 6: ...UTLET VENT HOT COLD HOT COLD HOT INLET WATER SUPPLY CISTERN TANK COLD MAINS SUPPLY MAX HEAD 40m VENT PIPE Stop Valve OVERFLOW PIPE Fig 03 Typical Vented Solar Installation Schematic 36005941_issue_07...

Страница 7: ...ure controller will control the operation of the solar pumped primary circuit to transfer heat from the solar collector panels to the cylinder via the lower solar primary coil heat exchanger refer to...

Страница 8: ...y doubt contact a competent electrician 5 3 Wiring All electrical wiring should be carried out by a competent electrician and be in accordance with the latest I E E Wiring Regulations The Megalife sol...

Страница 9: ...ns 1 5mm2 3 Core HOFR sheathed cable Indirect control wiring SPINDLE POSITIONS MINIMUM TEMP 10 C MAXIMUM TEMP 72 C APPROX 60 C ROTATE SPINDLE CLOCKWISE FOR TEMPERATURE INCREASE AND COUNTER CLOCKWISE F...

Страница 10: ...Supply 1 2 3 G 1 Br Bl 2 0 GY 3 G 1 Br Bl 2 0 1 3 2 2 L N Programmer Boiler Pump Zone valve HTG Cylinder terminal block Room stat Zone valve DHW Junction box 3 2 3 L 1 N 2 3 HTG ON DHW ON L N 2 3 1 L...

Страница 11: ...controls housing and its cable securely clamped Heating by the solar primary circuit is controlled by the solar differential temperature controller refer to the manufacturers installation instructions...

Страница 12: ...upply The temperature adjustment is made by inserting a flat bladed screwdriver in the slot in the spindle on top of the thermostat and rotating see Fig 05 page 9 If in any doubt consult a competent e...

Страница 13: ...laries by carefully pulling outwards from the immersion heater Note which order they are fitted Remove the terminal shroud Unscrew immersion heater backnut s and remove immersion heater from the unit...

Страница 14: ...model installed and ensure the correct part is ordered 9 Fault Finding and Servicing 2 9 6 4 5 8 3 1 Fig 08 Spares 10 Item Description Part Number 1 Immersion heater lower 95 606 984 2 Immersion heate...

Страница 15: ...low gradu ally decreases 1 Outlet flow rate exceeds inlet flow to cold water feed cistern 2 Flow starvation caused by opening further outlets 1 Install higher flow float valve Consider larger cold wat...

Страница 16: ...min at 80 C 2 C Temperature rise is from 15 C to 60 C Indirect units tested to BS EN 12897 2006 Type Model Reference Dimensions mm Solar Auxiliary Coil Solar Surface Area sq m Solar Coil Rating kW Rat...

Страница 17: ...per day kWh 24h per year kWh 365d 190 1 52 555 210 1 70 621 250 1 98 723 300 2 31 843 Indirect Model s CLV190 CLV210 CLV250 CLV300 Energy efficiency class C C C C Storage volume V in litres 190 210 2...

Страница 18: ...ckness 50mm Immersion heater Alloy sheathed element and thermostat pocket in Duplex stainless steel plate Pipe connections All connections accept 22mm outside diameter pipe compression nuts and olives...

Страница 19: ...e Republic of Ireland For installations outside these territories please contact either the Heatrae Sadia Heating Export Department Tel 44 1603 420191 or Baxi International Tel 44 1926 478323 for furt...

Страница 20: ...acles Harlow Essex CM19 5BT T 0845 055 3811 E sales ewh co uk SPD Units 9 10 Hexagon Business Centre Springfield Road Hayes Middlesex UB4 0TY T 020 8606 3567 Parts Center T 0845 270 9800 W www partsce...

Отзывы: