68
Rev. 05/2020
6) Properly clean Fan(s). (Refer to the “Air Supply” section of the Heatmor
TM
Operations
and Maintenance Manual.)
a) Turn off the main power supply to the furnace.
b) Loosen and remove the two thumb nuts securing the blower / flipper assembly to
the large air tube, and remove the blower / flipper assembly.
c) With a small brush, scrape any dust or residue that has accumulated on the fins
of the blower.
d) With a scraper or brush, remove any residue built up on the flipper assembly.
e) Ensure the flipper is resting completely on its seat. If it is not resting completely,
perhaps there is dust or soot built up on the flipper, or some other obstruction not
allowing it to close tightly.
f) Securely fasten the blower / flipper assembly back to the large air tube ensuring
there are no air leaks.
8)
Check the Heat Transfer Fluid (HTF) to make sure there is the appropriate amount of
DOWFROST™ HD mix in with your approved water. Refer to
“
Heat
Transfer Fluid
”
9) Take HTF sample and Mail to
HEATMOR™, Box 787, Warroad, MN 56763
as per
annual requirement to keep warranty valid
NOTE
: The HTF in the HEATMOR™ must be chemically analyzed once per year to ensure
the proper levels of treatment are being maintained. Provide 8-12 ounces in a clean
container and mail to HEATMOR™. When test results return, you must comply with any
instructions given by HEATMOR™ or it will void your warranty.