Heatilator NEVO3630I-B Скачать руководство пользователя страница 48

Heatilator  •  NEVO3630I-B, NEVO4236I-B Installation Manual  •  2378-980 Rev. E  •  4/16

48

F.  Install Glass Media

WARNING! Risk of Explosion! 

Follow glass media 

placement instructions. 
•  DO NOT place glass media in pilot opening. 
•  DO NOT place glass media where they might fall into 

pilot opening. 

•  DO NOT use any media other than the glass media 

supplied with this 

fi

 replace.

•  DO NOT place more than one layer of glass media on 

top of burner.

Improperly placed glass media interferes with proper 
burner operation. Delayed ignition could occur.

Install the Glass Media

•  Remove the screws holding the glass media placement 

jig. Leave the jig in place until the glass media is placed.

Figure 11.3  Remove Screws from Jig

•  Open the bag of glass media and place on the burner/

hearth pan area.

•  Spread the glass media over the entire area. 

Make 

sure glass media is only one layer thick on top of 
the burner

.

Jig

Glass Media

Figure 11.4  Place & Spread Glass Media

•  Remove the glass media placement jig.

•  Make sure the area in front of the pilot remains free of 

glass media.

Pilot opening must

be kept free of glass media

!

Figure 11.6  Pilot Open & Glass-Media-Free

Figure 11.5  Remove Jig

Cleaning the Glass Media

During shipment of the glass media, dust and debris can 
accumulate. We recommend the glass media be rinsed 
thoroughly with water to remove dust and small glass 
particles. 

•  Place the glass media into a bucket and rinse thoroughly 

with water. 

•  Allow the glass media to dry before installing it into the 

fi

 replace. 

WARNING! Choking Hazard!  

Keep glass media out of 

reach of children.

Содержание NEVO3630I-B

Страница 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could...

Страница 2: ...on A Vent Termination Minimum Clearances 12 B Chimney Diagram 13 C Approved Pipe 14 D Use of Elbows 15 E Measuring Standards 16 F Vent Diagrams 16 5 Vent Clearances and Framing A Pipe Clearances to Co...

Страница 3: ...____________ Switch wires properly installed ___________________________ Gas Section 9 Pg 43 44 Proper appliance for fuel type ___________________________ Was a conversion performed __________________...

Страница 4: ...cal authorities having jurisdiction for installations at elevations above 4500 feet 1370 m Check with your local gas utility to determine proper orifice size MODELS NEVO4236I B NEVO3630I B LABORATORY...

Страница 5: ...ication Materials made of or surfaced with wood compressed pa per plant fibers plastics or other material that can ignite and burn whether flame proofed or not or plastered or unplastered shall be con...

Страница 6: ...ed gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or loc...

Страница 7: ...and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling screws Caulking material 300 F minimu...

Страница 8: ...A 35 889 41 1041 B 30 762 36 914 C 6 3 8 162 6 3 8 162 D 19 7 8 505 19 7 8 505 E 26 5 8 676 32 5 8 829 F 31 1 2 800 31 1 2 800 G 39 1 8 994 39 1 8 994 H 15 3 4 400 15 3 4 400 I 1 3 4 44 1 3 4 44 J 23...

Страница 9: ...imensions Including Surround DF MR36 DF MR36 SS DECORATIVE FRONTS A B C D E F G H I NEVO3630i in 27 20 36 30 1 1 2 6 1 2 3 30 36 mm 686 508 914 762 38 165 76 762 914 G I H A B C D E F BOTTOM OF APPLIA...

Страница 10: ...m H As B increases H increases accordingly B Clearances to Combustibles When selecting a location for the appliance it is important to consider the required clearances to walls see Figure 3 3 WARNING...

Страница 11: ...on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe Insulation and other materials must be secu...

Страница 12: ...G 4 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep insulation or ot...

Страница 13: ...V V H Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap...

Страница 14: ...12 A for vent component information and dimensions DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requiremen...

Страница 15: ...imeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8 4 1 4 54 108 DV...

Страница 16: ...ounting Surface Figure 4 7 Measure to Top of Last Section of Pipe General Rules SUBTRACT 3 ft from the total H measurement for each 90 elbow installed horizontally SUBTRACT 1 1 2 ft from the total H m...

Страница 17: ...nt pipe when venting off the top of the appliance You must use a DVP SLP24 adapter or a DVP 2SL and two feet of DVP pipe which can only be attached to the appliance starting collar On horizontal termi...

Страница 18: ...16 18 Figure 4 11 One Elbow Top Vent Horizontal Termination continued H1 V1 V1 Minimum H1 Maximum 1 ft 305 mm 2 ft 610 mm 16 in 406 mm 4 ft 1 22 m 18 in 457 mm 6 ft 1 83 m 2 ft 610 mm 11 ft 3 35 m 30...

Страница 19: ...ure 4 12 Two or Three Elbows H1 V1 H2 H3 Installed Horizontally Installed Vertically H2 V1 Minimum H1 H2 Maximum H1 H2 H3 Maximum 18 in 457 mm 6 ft 1 83 m 3 ft 91 m 2 ft 610 mm 11 ft 3 35 m 8 ft 2 4 m...

Страница 20: ...tilator NEVO3630I B NEVO4236I B Installation Manual 2378 980 Rev E 4 16 20 Three Elbows Figure 4 13 H2 H1 V2 V1 Elbows Installed Vertically V1 min V1 V2 max H1 H2 max 2 ft 610 mm 25 ft 7 62 m 20 ft 6...

Страница 21: ...rations Remove screws holding flue visor to firebox top See Figure 4 14 Remove the flue visor Using the screws removed and the same holes install the top vent flue baffle and flue visor The top vent...

Страница 22: ...ure 4 17 Figure 4 18 Two Elbows Note If installing a vertical vent termination off the top of the ap pliance the flue restrictor should be used V1 V1 60 ft Max 18 3 m V1 12 ft Min 3 7 m Maximum horizo...

Страница 23: ...Installation Manual 2378 980 Rev E 4 16 Figure 4 19 Top Vent Vertical Termination continued Three Elbows Maximum horizontal run HTOTAL is 100 of vertical but cannot exceed 17 ft 5 18 m H1 H2 V1 V2 12...

Страница 24: ...e 45 Elbow H1 18 in 457 mm Maximum H1 9 in 229 mm Maximum H1 H1 REMOVE PILOT SHIELD NOTICE To ensure proper operation of appliance remove the pilot shield when the venting configuration includes a sin...

Страница 25: ...6 ft 1 8 m 6 ft 1 8 m 3 ft 914 mm 9 ft 2 7 m 8 ft 2 4 m 4 ft 1 2 m 12 ft 3 7 m 8 ft 2 4 m 5 ft 1 5 m 15 ft 4 6 m 8ft 2 4 m 6 ft 1 8 m 18 ft 5 5 m V1 H1 H2 50 ft 15 2 m Maximum H1 8 ft 2 4 m Maximum H...

Страница 26: ...Heatilator NEVO3630I B NEVO4236I B Installation Manual 2378 980 Rev E 4 16 26 Rear Vent Vertical Termination Figure 4 23 VTotal 12 ft 3 66 m min 60 ft 18 29 m max H1 0 min 6 ft 1 83 m max H1 VTotal...

Страница 27: ...Total 12 ft 3 66 m min VTotal 60 ft 18 29 m max H1 0 min H1 6 ft 1 83 m max HTotal Maximum horizontal run is 100 of vertical but cannot exceed 18 ft 5 5m VTotal 12 ft 3 66 m min VTotal 60 ft 18 29 m m...

Страница 28: ...ield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections B Wall Penetration Framing Firestops Combustible Wall Penetration Whenever a combustible wall is penetrated you must fr...

Страница 29: ...n around the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFOR...

Страница 30: ...6 3 Figure 6 4 Figure 6 5 Discard the vent cap remove and discard the insulation basket Note Once the vent cap has been removed it cannot be reattached Fold the center parts of the retaining band up a...

Страница 31: ...e 6 10 Fold the tabs toward the center of the vent cap 90 and remove the insulation gasket Cut the metal retaining band and fold the sides out Fold the center parts of the retaining band out and use t...

Страница 32: ...diagram shows how to properly position and secure the appliance See Figure 6 12 Nailing tabs are provided to secure the appliance to the framing members Bend out nailing tabs on each side Place the a...

Страница 33: ...direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 2 in 13 mm If pred...

Страница 34: ...to be sealed All unit collar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Figure 7 5 Adding Venting Components WARNING Risk of Fire or Explosion...

Страница 35: ...orted every 8 ft 2 44 m after the maximum allowed 25 ft 7 62 m of unsupported rise Vertical runs originating off the rear of the appliance or after any elbow must be supported every 8 ft 2 44 m Horizo...

Страница 36: ...CHARGE OPENING Figure 7 14 insert Bolt into Brackets Figure 7 14 insert Bolt into Brackets NOTICE Failure to properly caulk the roof flashing and pipe seams could permit entry of water Caulk the gap b...

Страница 37: ...lap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 16 If th...

Страница 38: ...surface of exterior wall see chart below Slip Section can be extended Inner Vent Outer Vent EXTERIOR Figure 7 16 Venting Through the Wall Cap Specification Chart depth without using additional pipe se...

Страница 39: ...nstall a shroud with this fireplace See Section 12 B for a list of UL Listed shrouds Follow the instructions included with these optional components Min Base Dim Min Base Dim Min Top Dim Min Top Dim F...

Страница 40: ...shell If the box is being wired from the INSIDE of the appliance Remove the screw attaching the junction box receptacle to the outer shell rotate the junction box inward to dis engage it from the out...

Страница 41: ...iance WARNING Risk of Shock or Explosion DO NOT wire IPI controlled appliance junction box to a switched circuit Incorrect wiring will override IPI safety lockout Refer to Figure 8 2 IPI Wiring Diagra...

Страница 42: ...tch box connect the black hot wire and red switch leg wire to the wall switch as shown At the appliance connect the black hot white neutral and green ground wires to the junction box as shown Add a 1...

Страница 43: ...pping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure could caus...

Страница 44: ...ger vertical runs See Figure 9 1 Turn the thumbscrew to open or close the air shutter It may be necessary to use a pliers or crescent wrench to adjust the shutter Note Adjust air shutter after flame h...

Страница 45: ...s using a 300 F minimum sealant Refer to Figure 10 1 WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specifi...

Страница 46: ...izontal Dimensions of Combustibles Note Mantel Measurement is taken from top of the opening NOT the top of the fireplace 1 in 25 mm min to perpendicular wall A 3 1 2 in 89 mm min from fireplace openin...

Страница 47: ...be factory installed or accompany the door of the unit depending on the fireplace model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in st...

Страница 48: ...emove Screws from Jig Open the bag of glass media and place on the burner hearth pan area Spread the glass media over the entire area Make sure glass media is only one layer thick on top of the burner...

Страница 49: ...chnologies if the barrier is not present or help is needed to properly install one For more information refer to the instructions supplied with your decorative front G Install Fixed Glass Assembly WAR...

Страница 50: ...8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height...

Страница 51: ...1 2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall...

Страница 52: ...m RF12 Roof Flashing Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Bri...

Страница 53: ...in 12 in 305 mm 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 4...

Страница 54: ...Wire Harness PVI WH40 60 FT PV Wire Harness PVI WH60 80 FT PV Wire Harness PVI WH80 100 FT PV Wire Harness PVI WH100 PVI SLP Power Vent Inline SLP LPC SLP Low Profile Cap Note Wire harnesses required...

Страница 55: ...e ordered separately from PVLP SLP Contact your dealer to order Note The PVLP SLP requires a PVLP CK be installed on this appliance The PVLP CK is ordered separately from the PVLP SLP Contact your dea...

Страница 56: ...ht Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8 in 22...

Страница 57: ...ield trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm T...

Страница 58: ...34 mm 10 9 16 in 269 mm 14 in 356 mm 12 1 2 in 318 mm 12 in 305 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical T...

Страница 59: ...in 432 mm 9 3 8 in 238 mm TCG375 Terra Cotta Cap LDSCP M Shroud Leg Multipack not shown See your Heatilator dealer for a complete listing of optional components B Optional Components Catalog A B C D...

Страница 60: ...Follow the instructions supplied with the control installed to operate your fireplace For safety Install a switch lock or a wall remote control with child protection lockout feature Keep remote contr...

Отзывы: