Heatilator • NEVO3630I-B, NEVO4236I-B Installation Manual • 2378-980 Rev. E • 4/16
38
Note:
When using termination caps with factory-supplied
heat shield attached, no additional wall shield
fi
restop is
required on the exterior side of a combustible wall.
Install Horizontal Termination Cap (DVP and
SLP Pipe)
WARNING! Risk of Fire!
The telescoping
fl
ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of
fl
ue telescoping
section is required.
Failure to maintain overlap could cause overheating and
fi
re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1
and
CAN/CGA-B149
installation codes
and refer to Section 4 of this manual.
INTERIOR
Heat Shield or
Extended
Heat Shield
Wall Shield
Firestop
Heat Shield
1-1/2 in. (38 mm) min.
overlap
SHEATHING
Vent depth from back of appliance to
outside surface of exterior wall
(see chart below)
Slip Section
can be extended
Inner Vent
Outer Vent
EXTERIOR
Figure 7.16 Venting Through the Wall
Cap Speci
fi
cation Chart (depth without using additional pipe sections)
NEVO Series
DVP-TRAPK1
Top Vent Depth
DVP-TRAP1
Rear Vent Depth
DVP-TRAPK2
Top Vent Depth
DVP-TRAP2
Rear Vent Depth
SLP-TRAP1
Top Vent Depth
SLP-TRAP2
Top Vent Depth
4 1/2 to 6 3/8 in.
3 to 4 7/8 in.
6 7/8 to 10 7/8 in.
5 3/8 to 9 3/8 in.
2 to 3 7/8 in.
4 3/8 to 8 3/8 in.
DVP-HPC1
Top Vent Depth
DVP-HPC1
Rear Vent Depth
DVP-HPC2
Top Vent Depth
DVP-HPC2
Rear Vent Depth
4 1/2 to 6 5/8 in.
3 to 5 1/8 in.
6 5/8 to 10 3/4 in.
5 1/8 to 9 1/4 in.
DVP-TRAP1 can adjust 1 1/2 in. (3 1/8 to 4 5/8)
DVP-TRAP2 can adjust 4 in. (5 3/8 to 9 3/8)
SLP-TRAP1 can adjust 1 5/8 in. (3 1/8 to 4 3/4)
SLP-TRAP2 can adjust 4 in. (5 1/4 to 9 1/4))
DVP-HPC1 can adjust 2 1/8 in. (4 1/4 to 6 3/8)
DVP-HPC2 can adjust 4 1/8 in. (6 3/8 to 10 1/2)
CAUTION! Risk of Burns!
Local codes may require in-
stallation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE:
For certain exposures which require superior
resistance to wind-driven rain penetration, a
fl
ashing kit
and HRC caps are available. When penetrating a brick
wall, a brick extension kit is available for framing the brick.