Heatilator  • NDV30-IFT, NDV33-IFT, NDV36-IFT, NDV36-IFT-NVR, NDV42-IFT Installation Manual  •  2620-980  Rev. C  •  8/20 

6

I.  Requirements for the Commonwealth of 

Massachusetts

For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in 

whole or in part for residential purposes, including those 

owned or operated by the Commonwealth and where the 

side wall exhaust vent termination is less than seven (7) 

feet above finished grade in the area of the venting, in

-

cluding but not limited to decks and porches, the following 

requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter 

shall observe that a hard wired carbon monoxide detector 

with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addi-

tion, the installing plumber or gas fitter shall observe that 

a battery operated or hard wired carbon monoxide detec-

tor with an alarm is installed on each additional level of 

the dwelling, building or structure served by the side wall 

horizontal vented gas fueled equipment. It shall be the 

responsibility of the property owner to secure the services 

of  qualified  licensed  professionals  for  the  installation  of 

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery  back-up  may  be  installed  on  the  next  adjacent 

floor level.

In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply 

with the above requirements; provided, however, that dur-

ing said thirty (30) day period, a battery operated carbon 

monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor-

dance with the above provisions shall comply with NFPA 

720 and be ANSI/UL 2034 listed and IAS certified. 

Signage

A metal or plastic identification plate shall be permanent

-

ly mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the 

exhaust vent terminal for the horizontally vented gas fu-

eled heating appliance or equipment. The sign shall read, 

in print size no less than one-half (1/2) in. in size, 

“GAS 

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon-

tally vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector ob-

serves carbon monoxide detectors and signage installed 

in accordance with the provisions of 248 CMR 5.08(2)(a)1 

through 4. 

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)

(a)1 through 4: 
•  The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and 

•  Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure separate 

from the dwelling, building or structure used in whole or 

in part for residential purposes. 

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall 

horizontally vented gas equipment provides a venting 

system design or venting system components with the 

equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system 

shall include:
•  Detailed instructions for the installation of the venting 

system design or the venting system components; and

•  A complete parts list for the venting system design or 

venting system. 

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not pro-

vide  the  parts  for  venting  the  flue  gases,  but  identifies 

“special  venting  systems”,  the  following  requirements 

shall be satisfied by the manufacturer:

•  The  referenced  “special  venting  system”  instructions 

shall be included with the appliance or equipment in-

stallation instructions; and 

•  The  “special  venting  systems”  shall  be  Product  Ap

-

proved by the Board, and the instructions for that sys-

tem shall include a parts list and detailed installation 

instructions. 

A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equip-

ment, all venting instructions, all parts lists for venting 

instructions, and/or all venting design instructions shall 

remain with the appliance or equipment at the completion 

of the installation. 

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

Note: 

The following requirements reference various 

Massachusetts and national codes not contained in this 

document.

Содержание NDV30-IFT

Страница 1: ...ly call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a...

Страница 2: ...Location and Clearances to Combustibles 13 C Constructing the Appliance Chase 16 4 Termination Location and Vent Information A Approved Pipe 17 B Vent Termination Minimum Clearances 17 C Vent Terminal...

Страница 3: ...Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check performed and inlet pressure verified ___________________________ Verified...

Страница 4: ...not be factored as primary heat in residential heating calculations NOTICE This installation must conform with local codes In the absence of local codes you must comply with the National Fuel Gas Code...

Страница 5: ...fed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in t...

Страница 6: ...rizontally vented gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection T...

Страница 7: ...sure that the following tools and building supplies are available Hand Tools Tape measure Level Framing material Manometer Framing square Voltmeter Electric drill and bits 1 4 in Plumb line Safety gl...

Страница 8: ...r water Carefully remove the appliance and components from the packaging The vent system components and decorative barrier fronts may be shipped in separate packages If packaged separately the log set...

Страница 9: ...2 32 5 8 829 38 5 8 981 F 31 1 2 800 31 1 2 800 31 1 2 800 31 1 2 800 G 35 1 4 895 35 1 4 895 35 1 4 895 35 1 4 895 H 15 3 4 400 15 3 4 400 15 3 4 400 15 3 4 400 I 1 3 4 44 1 3 4 44 1 3 4 44 1 3 4 44...

Страница 10: ...9 518 835 48 171 762 803 DEMI36 B in 32 7 8 20 3 8 35 7 8 1 7 8 6 3 4 30 31 5 8 mm 835 518 911 48 171 762 803 DEMI42 B in 38 7 8 20 3 8 41 7 8 1 7 8 6 3 4 30 31 5 8 mm 987 518 1064 48 171 762 803 IMPO...

Страница 11: ...9 533 835 48 171 762 803 TRES36 B in 32 7 8 21 35 7 8 1 7 8 6 3 4 30 31 5 8 mm 835 533 911 48 171 762 803 TRES42 B in 38 7 8 21 41 7 8 1 7 8 6 3 4 30 31 5 8 mm 987 533 1064 48 171 762 803 IMPORTANT Th...

Страница 12: ...5 8 2 3 8 30 31 1 2 mm 873 533 911 41 60 762 800 SIM 4842 in 40 3 8 21 41 7 8 1 5 8 2 3 8 30 31 1 2 mm 1026 533 1064 41 60 762 800 Figure 3 4 Decorative Barrier Front Dimensions SIMON B IMPORTANT This...

Страница 13: ...to combustibles 2 Alcove Installation C 1 in 25 mm min pipe to combustibles G Drywall 48 in 1219 mm maximum NOTE Consider the mantel or cabinet system to be installed and comply with the necessary re...

Страница 14: ...z Term 6 Rear Vent Two 90 elbows Horiz Term 4 Rear Vent One 90 elbow Vert Term 1 Top Vent One 90 elbow Horiz Term 5 No elbows Horiz Term A A A A A A C B B E F D 1 2 in 13 mm min appliance to combustib...

Страница 15: ...ble flooring may be installed next to the front of the appliance Drywall 1 2 in 13 mm 1 2 in 13 mm C A B Note If the inside of the framed cavity is to be finished the framing dimensions must include t...

Страница 16: ...nd wall shield firestops and construction of the chase may vary with the type of building These instructions are not substitutes for the requirements of local building codes Therefore you MUST check l...

Страница 17: ...n or other materials away from vent pipe could cause overheating and fire WARNING Figure 4 2 Staggered Termination Caps H minimum may vary depending on regional snowfall Refer to local codes A Approve...

Страница 18: ...to building or the combustion air inlet to any other appliance termination mechanical or non mechanical 9 in 229 mm 12 in 305 mm I clearance to a mechanical powered air supply inlet All mechanical ai...

Страница 19: ...Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 914 25 1 2 648 DVP48 48 1219 34 864 DVP6A 3 to 6 76 to 152 2 1 8...

Страница 20: ...gure 4 9 Measure to Top of Last Section of Pipe E Vent Diagrams Figure 4 7 Water Infiltration Prevention 1 4 in max 6 mm W A L L General Rules A maximum of three 90 elbows or six 45 elbows may be used...

Страница 21: ...T NDV36 IFT NDV36 IFT NVR NDV42 IFT Installation Manual 2620 980 Rev C 8 20 Figure 4 10 Measure Horizontal and Vertical Termination Clearance to Trapezoid Portion of Cap OVERHANG C E WALL C and E dime...

Страница 22: ...s appliances can adapt to SLP series vent pipe when venting off the top of the appliance You must use a DVP SLP24 adapter or a DVP 2SL and two feet of SLP pipe which can only be attached to the applia...

Страница 23: ...T 0 0 24 in 610 mm 18 in 457 mm 4 in 102 mm 4 ft 1 22 m 4 ft 1 22 m 6 in 152 mm 6 ft 1 83 m 6 ft 1 83 m 12 in 305 mm 11 ft 3 35 m 11 ft 3 35 m 18 in 457 mm 18 ft 5 49 m 18 ft 5 49 m 24 in 610 mm 25 ft...

Страница 24: ...lly H1 V1 H2 H3 Installed Horizontally Installed Vertically H2 V1 Minimum H1 H2 Maximum H1 H2 H3 Maximum 6 in 152 mm 6 ft 1 83 m 3 ft 91 m 12 in 305 mm 11 ft 3 35 m 8 ft 2 4 m 18 in 457 mm 18 ft 5 49...

Страница 25: ...NDV42 IFT Installation Manual 2620 980 Rev C 8 20 Three Elbows H2 H1 V2 V1 Elbows Installed Vertically V1 min V1 V2 max H1 H2 max 12 in 305 mm 25 ft 7 62 m 19 ft 5 79 m V1 V2 H1 H2 44 ft 13 41 m Maxi...

Страница 26: ...12 30 Ft Vertical Run Figure 4 19 31 60 Ft Vertical Run Install Top Vent Flue Visor No Elbow Configurations Remove screws holding flue visor to firebox top See Figure 4 17 Remove the flue visor Using...

Страница 27: ...T NVR NDV42 IFT Installation Manual 2620 980 Rev C 8 20 Three Elbows Maximum horizontal run HTOTAL is 100 of vertical but cannot exceed 26 ft 7 92 m H1 H2 V1 V2 6 ft 1 83 m min 60 ft 18 29 m max V2 V1...

Страница 28: ...allation Manual 2620 980 Rev C 8 20 28 Four Elbows Figure 4 21 H1 V2 V1 Elbows Installed Vertically H2 V3 Maximum horizontal run HTOTAL is 100 of vertical but cannot exceed 23 ft 7 01 m V1 V2 V3 6 ft...

Страница 29: ...y Note Use DVP Series components only WARNING Risk of Fire This vent configuration is not allowed with NDV42 IFT NDV42L IFT H1 Note To achieve optimum flame appearance the vent configurations shown in...

Страница 30: ...ft 610 mm 4 ft 1 2 m 6 ft 1 8 m 3 ft 914 mm 6 ft 1 8 m 9 ft 2 7 m 4 ft 1 2 m 8 ft 2 4 m 12 ft 3 7 m 5 ft 1 5 m 8 ft 2 4 m 15 ft 4 6 m 6 ft 1 8 8 ft 2 4 m 18 ft 5 5 m V1 Minimum H1 Maximum HTotal 1 ft...

Страница 31: ...v C 8 20 Figure 4 26 Figure 4 27 Rear Vent Vertical Termination One Elbow Two Elbows VTotal 6 ft 1 83 m min 60 ft 18 29 m max H1 0 min 6 ft 1 83 m max H1 VTotal 6 ft 1 83 m min 60 ft 18 29 m max 0 min...

Страница 32: ...lation Manual 2620 980 Rev C 8 20 32 Rear Vent Vertical Termination continued Three Elbows Figure 4 28 VTotal 6 ft 1 83 m min VTotal 60 ft 18 29 m max H1 0 min H1 6 ft 1 83 m max HTotal Maximum horizo...

Страница 33: ...s 1 in 25 mm Note Heat shields MUST overlap by a minimum of 1 1 2 in 38 mm DVP heat shield designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in the...

Страница 34: ...p on both sides then both wall shield firestops must have a heat shield refer to Section 12 A attached to them See Section 7 F for information for regarding the instal lation of a horizontal terminati...

Страница 35: ...th nails or screws WARNING Risk of Fire DO NOT pack insu lation around the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Inst...

Страница 36: ...ver plate by removing the two screws holding it to the top of the appliance Remove and discard the cover plate Remove the center insulation plug Cut the metal retaining band and fold the sides out Fol...

Страница 37: ...tach the first vent section it will snap into place Slide the insulation gasket onto the vent section up against the appliance and over the tabs Discard the vent cap remove and discard the insulation...

Страница 38: ...ces are required for heat management systems installations Provisions must be made in advance to ensure fit within the framing Heat management systems include Heat Zone Gas and Heat Out Gas Other syst...

Страница 39: ...ces Lances WARNING Risk of Fire or Explosion Vent sections MUST be installed correctly Improperly installed vent sections could leak or cause appliance to overheat Attach Vent to the Firebox Assembly...

Страница 40: ...All unit collar pipe slip section elbow and cap outer flues shall be sealed in this manner unless otherwise stated Assemble Vent Sections SLP Only To attach the first vent component to the starting c...

Страница 41: ...ter flues of the slip section can be cut to the desired length Maintain a 1 1 2 in 38 mm overlap between the slip section and the pipe section Secure the pipe and slip section with two screws no longe...

Страница 42: ...pipe sections extending through the roof as shown in Figure 7 12 Use an elastomeric or silicone sealant with a minimum of 150 F temperature rating to seal the metal roof flashing NOTICE Failure to pr...

Страница 43: ...the heat shields attached to the wall shield firestop and the horizontal termination cap shown in Figure 7 15 Heat shields must overlap 1 1 2 in 38 mm mini mum There are two sections of the heat shie...

Страница 44: ...rom touching the hot cap NOTICE For certain exposures which require superior resistance to wind driven rain penetration a flashing kit and HRC caps are available When penetrating a brick wall a brick...

Страница 45: ...tall a shroud with this fireplace See Section 12 B for a list of UL Listed shrouds Follow the instructions included with these optional components Min Base Dim Min Base Dim Min Top Dim Min Top Dim Fig...

Страница 46: ...nection when servicing controls Wiring errors could cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105 C rated wire...

Страница 47: ...Wiring Diagram This appliance is equipped with an IntelliFire control valve which operates on a 6 volt system B Wiring Requirements FLAME SENSE 2090 012 NG 2090 013 P IGNITER ADAPTER 2326 131 I S 6 P...

Страница 48: ...n can be used in conjunction with a wall mounted switch See Figure 8 3 To control fan speed a BC10 Blower Control Wall Switch must be used The power supply for the appliance must be brought into a swi...

Страница 49: ...t pressure 10 0 in w c 13 0 in w c Manifold pressure 3 5 in w c 10 0 in w c D High Altitude Installations NOTICE If the heating value of the gas has been reduced these rules do not apply Check with yo...

Страница 50: ...ter See chart below for correct shutter settings The shutter measurement is taken from the bottom of the tub to the bottom of the thumbscrew See Figure 9 1 Note Adjust air shutter after flame has reac...

Страница 51: ...stible Mantel Legs or Wall Projections Figure 10 1 Minimum Vertical and Maximum Horizontal Dimensions for Combustible Mantels Note Mantel Measurement is taken from top of the opening NOT the top of th...

Страница 52: ...tel Leg or Wall Projections Acceptable on both sides of opening Non Combustible Mantel Legs or Wall Projections Figure 10 3 Minimum Vertical and Maximum Horizontal Dimensions for Non Combustibles Mant...

Страница 53: ...proper burner operation Note It may be helpful to temporarily remove Log 5 to place the mineral wool If removed replace log according to log placement instructions Mineral wool is shipped with this g...

Страница 54: ...h care Inspect the gasket to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken o...

Страница 55: ...left end of Log 4 into the flat spot on Log 2 and then resting the right end or nose of Log 4 on the flat spot on Log 1 Figure 3 shows locations of flat spots Figure 4 shows Log 4 installed 4 4 SIZE 3...

Страница 56: ...of Log 5 is positioned toward the front of the appliance with the two slots on the back side resting on the bent lip of the hearth pan See Figure 6 Slide Log 5 toward the right until it contacts the...

Страница 57: ...in 187 mm 11 3 8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart E...

Страница 58: ...ld is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than...

Страница 59: ...S 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Brick Extension 13 7 8 in 352 mm 5 in 127 mm...

Страница 60: ...ation Cap 7 1 4 in 12 in 305 mm 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41...

Страница 61: ...87 Effective Length 5 3 4 to 8 3 8 in 146 to 213 mm 5 1 2 in 140 mm 8 3 8 in 213 mm DVP HRC ZC SS NOT APPROVED FOR ALL UNITS Not approved for NDV42 IFT Figure 12 5 PVI SLP B Vent Components DECORATIVE...

Страница 62: ...SLEEVE 48 A Vent Components Diagrams continued PVV SLP Vertical Power Vent Note A wire harness is required to power the PVV SLP and connect it to the appliance It is ordered separately from the PVV S...

Страница 63: ...mm 13 5 8 IN 346 mm EFFECTIVE LENGTH 32 IN 813 mm MIN 35 IN 889 mm MAX Figure 12 7 PVI SLP B Vent Components PVI SLP B Power Vent Inline SLP LPC SLP Low Profile Cap Approved for use with PVI SLP B on...

Страница 64: ...21 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View PVLP BEK Brick Kit Note Wire harnesses required to power the PVLP SLP connect to the appliance and are ordered separat...

Страница 65: ...Effective Height Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276...

Страница 66: ...kness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Trap2 5 1 4 in 9 1 4 in 13...

Страница 67: ...n 356 mm 12 1 2 in 318 mm 12 in 305 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW Vertical Termination Cap DVP FBHT Hori...

Страница 68: ...20 in 508 mm 17 in 432 mm 9 3 8 in 238 mm TCG375 Terra Cotta Cap LDSCP M Shroud Leg Multipack not shown See your Heatilator dealer for a complete listing of optional components B Optional Components C...

Страница 69: ...may be added Contact your dealer to order the correct refractory kit Detailed installa tion instructions are included with the refractory kit Remote Controls Wall Controls and Wall Switches After a q...

Отзывы: